2007-04-20 15:54:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 REGARDING THE LETTER PREPARED BY JOHN HOLT, PE, NOTE
 THE FOLLOWING:
  
 1.THE ENGINEERING DOES NOT REFER TO THE NOA.PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 2.THE ENGINEER STATES THAT THE CORNER IS 4" EACH
 DIRECTION.PLEASE REVISE, SEE FBC R 301.
  
 3.THE ENGINEER STATES THAT THE LAP NAILING IS 3", 4"
 IS THE MINIMUM SPACING, RAS117.
  
 4.THE ENGINEER STATES THAT THE CORNERIS TO HAVE 5
 1/2INCH SPACING.RAS117 REQUIRES THAT NAILING BE
 ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 5.THE ENGINEER STATES THAT HE IS USING 140 EXPOSURE C
 PRESSURES.ASCE7-02 OR FBC TABLE 1609.6.2.1(2)?
 ENGINEER DOES NOT SPECIFY DESIGN PRESSURES, SO I CANNOT
 DETERMINE WHETHER OR NOT ENHANCED FASTENING FOR ZONE 2,
 PERIMETER, IS REQUIRED.ENGINEER SPECIFIES ONLY THE
 FIELD AND CORNER, ZONES 1 AND 3.
  
 6.THE FIELD FASTENING SPECIFIED BY THE ENGINEER IS
 NOT COMPLIANT FOR THE ASSEMBLY THE CONTRACTOR HAS
 SELECTED.AS THE ENGINEER DOES NOT REFERENCE ANY NOA
 OR ASSEMBLY, DOES HE INTEND THAT THIS FASTENING IS FOR
 ANY ROOF SYSTEM?MOST HAVE FASTENING CLOSER THAN
 10INCHES.
  
 7.SEE GENERAL LIMITATION #7.PROVIDE CALCULATIONS IN
 ACCORDANCE WITH RAS117.
  
 A SET HAS BEEN RETAINED.
  