2008-01-16 10:52:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.FROM PREVIOUS LIST, NOT ADDRESSED - A DESIGN
 PRESSURE OF -79 REQUIRES USE OF THE 100PSF ROW, SHEET 6
 OF THE PRODUCT APPROVAL.11" MINIMUM ANCHOR SPACING
 REQUIRED.PLEASE REVISE INSTALLATION SCHEDULE.
  
 2ND REVIEW, INSTALLATION SCHEDULE STILL SPECIFIES 12".
  
  
 2.THE ENGINEERING SUBMITTED IS FOR EXPOSURE B, THIS
 JOB IS IN EXPOSURE C, FBC1609.6.2.1(2).
  