2007-04-19 10:49:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ***ONLY CHECKED ITEMS APPLY***
  
 _XX_1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 _XX_2.THE DESIGN PRESSURE FOR THE WINDOW (SEE
 SHEETS 1 AND 2, -110) DOES NOT MEET THE DESIGN PRESSURE
 SPECIFIED BY THE ENGINEER (-143.9).
  
 _XX_3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.MARK THE MULLION PRODUCT APPROVAL TO SHOW
 WHICH PRODUCT YOU ARE USING.NOTE THAT FOR A 80" WIDE
 OPENING (37+37=74), 63 INCHES HIGH, 1X4 IS LIMITED TO
 DESIGN PRESSURE OF -128, BUT THE ENGINEER SPECIFIES
 -143.9.
  
 _XX_5..)PRODUCT APPROVALS ARE TO BE APPROVED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW
 LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 505.1.
  
 _XX_7.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.(SHUTTERS)
  
  