2007-04-19 10:49:26 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FACFLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| ***ONLY CHECKED ITEMS APPLY*** |
| |
| _XX_1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| |
| _XX_2.THE DESIGN PRESSURE FOR THE WINDOW (SEE |
| SHEETS 1 AND 2, -110) DOES NOT MEET THE DESIGN PRESSURE |
| SPECIFIED BY THE ENGINEER (-143.9). |
| |
| _XX_3.PROVIDE A COPY OF THE CONDO ASSOCIATION |
| APPROVAL. |
| |
| _XX_4.MARK THE MULLION PRODUCT APPROVAL TO SHOW |
| WHICH PRODUCT YOU ARE USING.NOTE THAT FOR A 80" WIDE |
| OPENING (37+37=74), 63 INCHES HIGH, 1X4 IS LIMITED TO |
| DESIGN PRESSURE OF -128, BUT THE ENGINEER SPECIFIES |
| -143.9. |
| |
| _XX_5..)PRODUCT APPROVALS ARE TO BE APPROVED BY |
| DESIGNER OF RECORD, FBC*106.3.3. |
| |
| ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW |
| LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE |
| EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE |
| FOR BEDROOMS, FBC R310, FBC EB 505.1. |
| |
| _XX_7.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| ANOTHER FORMAT.(SHUTTERS) |
| |
| |