Plan Review Notes For Permit 07040341 |
Permit Number |
07040341 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-02-27 11:02:21 | REVISION #2: "OK" BBQ DESIGNATED "FUTURE" APPLIANCE AND | | CAPPED GAS TIGHT. | | | | | | ****************PROVISO**************** | | A}FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF | | GENERATOR PLACEMENT. | | NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET | | CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES | | SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS | | 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR | | TO FINAL INSPECTION. | | | | B} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED | | PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,000 CUBIC FEET REQUIRED. |
|