2007-04-23 08:56:44****************PROVISO****************
 A}FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 B} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED
 PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.