Plan Review Notes For Permit 07040339 |
Permit Number |
07040339 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-13 13:49:29 | ***DENIED*** | | | | 1) PLEASE CLARIFY IF BUILDING IS PROTECTED BY AUTOMATIC | | FIRE SPRINKLER SYSTEM. | | | | 2) FIRE ALARM NOTES REFERENCE FIRE SPRINKLER EQUIPMENT. | | IF APPLICABLE, PLEASE SHOW LOCATION ON DRAWINGS AS | | ELECTRONIC EQUIPMENT WOULD BE PART OF THIS SCOPE OF | | WORK. | | | | 3) PLEASE ILLUSTRATE FLOW AND TAMPER DEVICES ON RISER | | DIAGRAM IN ADDITION TO THE DRAWINGS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|