Plan Review Notes
Plan Review Notes For Permit 07040339
Permit Number 07040339
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-13 13:49:29***DENIED***
  
 1) PLEASE CLARIFY IF BUILDING IS PROTECTED BY AUTOMATIC
 FIRE SPRINKLER SYSTEM.
  
 2) FIRE ALARM NOTES REFERENCE FIRE SPRINKLER EQUIPMENT.
 IF APPLICABLE, PLEASE SHOW LOCATION ON DRAWINGS AS
 ELECTRONIC EQUIPMENT WOULD BE PART OF THIS SCOPE OF
 WORK.
  
 3) PLEASE ILLUSTRATE FLOW AND TAMPER DEVICES ON RISER
 DIAGRAM IN ADDITION TO THE DRAWINGS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756