Plan Review Notes
Plan Review Notes For Permit 07040257
Permit Number 07040257
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-28 07:20:39BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)INDICATE ON THE DRAWINGS THE TOTAL SQUARE FOOTAGE
 OF THE POOL DECK. ALSO STATE WHAT TYPE OF DECK WILL BE
 INSTALLED FOR RECORD PURPOSES.
  
 2)R4101.17.1 OUTDOOR SWIMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH R4101.17.1.1 THROUGH
 R4101.17.1.14. STATE ON THE DRAWINGS WHICH TYPE OF
 SAFETY FEATURE WILL BE INSTALL. FBC 13-612.1.ABC.2.3.2
 COVERS REQUIRED. SPAS AND HEATED SWIMMING POOLS SHALL
 BE
 EQUIPPED WITH A COVER DESIGNED TO MINIMIZE HEAT LOSS.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD),MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  