Plan Review Notes For Permit 07040257 |
Permit Number |
07040257 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-28 07:20:39 | BUILDING PLAN REVIEW | | PERMIT: | | ADD: | | CONT: | | TEL: (561)###-#### | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1)INDICATE ON THE DRAWINGS THE TOTAL SQUARE FOOTAGE | | OF THE POOL DECK. ALSO STATE WHAT TYPE OF DECK WILL BE | | INSTALLED FOR RECORD PURPOSES. | | | | 2)R4101.17.1 OUTDOOR SWIMING POOLS SHALL BE PROVIDED | | WITH A BARRIER COMPLYING WITH R4101.17.1.1 THROUGH | | R4101.17.1.14. STATE ON THE DRAWINGS WHICH TYPE OF | | SAFETY FEATURE WILL BE INSTALL. FBC 13-612.1.ABC.2.3.2 | | COVERS REQUIRED. SPAS AND HEATED SWIMMING POOLS SHALL | | BE | | EQUIPPED WITH A COVER DESIGNED TO MINIMIZE HEAT LOSS. | | | | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | (BVD),MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | PER 108.3 FBC* | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | | | |
|