Plan Review Notes For Permit 07040226 |
Permit Number |
07040226 |
|
Review Stop |
B |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2007-07-26 10:21:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)COMMENT FROM FIRST TWO LISTS, REVISE EXPOSURE | | CATEGORY. ON THE INSTALLATION SCHEDULE YOU'VE STATED | | THAT THIS IS EXPOSURE C BUT RAN WIND LOAD SOFTWARE AS | | EXPOSURE B. THE PRESSURES SHOULD BE OVER -40PSF.THE | | ANCHOR SPACING YOU HAVE SPECIFIED IS NOT COMPLIANT FOR | | EXPOSURE C. | | | | NEW COMMENT: | | | | 2.)PROVIDE TWO IDENTIAL COLLATED SETS FOR PERMIT | | ISSUANCE. | | |
|