Plan Review Notes For Permit 07040226 |
Permit Number |
07040226 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-07-06 10:14:05 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)COMMENT FROM FIRST LIST, REVISE EXPOSURE CATEGORY. | | ON THE INSTALLATION SCHEDULE YOU'VE STATED THAT THIS IS | | EXPOSURE C BUT RAN WIND LOAD SOFTWARE AS EXPOSURE B. | | THE PRESSURES SHOULD BE OVER -40PSF.THE ANCHOR | | SPACING YOU HAVE SPECIFIED IS NOT COMPLIANT FOR | | EXPOSURE C. | | |
|