2007-06-11 15:56:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
  
 1.)THE SHUTTER MOUNTING CONNECTION TYPE (A THROUGH L,
 PAGES 14-15) SHOULD REFER TO THE SPECIFIC CONNECTION
 TYPE FOR THAT OPENING (NOT THE ANCHOR).
  
 CONNECTION TYPES G AND H ARE CIRCLED ON THE PRODUCT
 APPROVAL.IT SHOULD BE ON THE INSTALLATION SCHEDULE,
 ESPECIALLY AS THE ANCHORING CIRCLED IS NOT CONSISTENT
 WITH THE ANCHORING ON THE SCHEDULE.
  
 2.)FLOOR MOUNT, H, REQUIRES 8.5" SPACING, BUT THE
 INSTALLATION SCHEDULE SPECIFIES 10" FOR THE BOTTOM
 TRACK.PLEASE COMPLETE THE INSTALLATION SCHEDULE (SEE
 ITEM 1 ABOVE) AND CONFIRM THAT ANCHOR SPACING ON THE
 SCHEDULE IS CONSISTENT WITH THE CONNECTION TYPE YOU ARE
 USING.