Plan Review Notes
Plan Review Notes For Permit 07040179
Permit Number 07040179
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-12 12:53:43 
  
  
 680.26(B) BONDED PARTS THE PARTS SPECIFIED IN
 680.26(B)(1) THROUGH (B)(5) SHALL BE BONDED TOGETHER.
 THE METAL PARTS REQUIRED TO BE BONDED PER 680.26(B)
 INCLUDE ALL METAL PARTS OF ELECTRICAL EQUIPMENT
 ASSOCIATED WITH THE WATER-CIRCULATING SYSTEM OF THE
 POOL, ALL METAL PARTS OF THE POOL STRUCTURE, AND ALL
 FIXED METAL PARTS, WHICH INCLUDE CONDUIT AND PIPING,
 METAL DOOR FRAMES, AND METAL WINDOW FRAMES, WITHIN 5 FT
 OF THE INSIDE WALLS OF THE POOL AND NOT SEPARATED BY A
 PERMANENT BARRIER. THE BONDING OF THESE PARTS DOES NOT
 MEAN THEY ARE REQUIRED TO BE CONNECTED TO EACH OTHER;
 RATHER, IT MEANS THEY ARE REQUIRED TO BE CONNECTED TO A
 COMMON BONDING GRID BY USING AN INSULATED, COVERED, OR
 BARE SOLID COPPER CONDUCTOR NOT SMALLER THAN 8 AWG OR
 BY USING BRASS OR OTHER CORROSION-RESISTANT METAL
 CONDUIT. SEE EXHIBIT 680.11. CONNECTIONS ARE REQUIRED
 TO BE MADE BY EXOTHERMIC WELDS OR BY LISTED PRESSURE
 CONNECTORS, CLAMPS, OR OTHER LISTED MEANS, IN
 ACCORDANCE WITH 250.8.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]