Plan Review Notes For Permit 07040179 |
Permit Number |
07040179 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-12 12:53:43 | | | | | | | 680.26(B) BONDED PARTS THE PARTS SPECIFIED IN | | 680.26(B)(1) THROUGH (B)(5) SHALL BE BONDED TOGETHER. | | THE METAL PARTS REQUIRED TO BE BONDED PER 680.26(B) | | INCLUDE ALL METAL PARTS OF ELECTRICAL EQUIPMENT | | ASSOCIATED WITH THE WATER-CIRCULATING SYSTEM OF THE | | POOL, ALL METAL PARTS OF THE POOL STRUCTURE, AND ALL | | FIXED METAL PARTS, WHICH INCLUDE CONDUIT AND PIPING, | | METAL DOOR FRAMES, AND METAL WINDOW FRAMES, WITHIN 5 FT | | OF THE INSIDE WALLS OF THE POOL AND NOT SEPARATED BY A | | PERMANENT BARRIER. THE BONDING OF THESE PARTS DOES NOT | | MEAN THEY ARE REQUIRED TO BE CONNECTED TO EACH OTHER; | | RATHER, IT MEANS THEY ARE REQUIRED TO BE CONNECTED TO A | | COMMON BONDING GRID BY USING AN INSULATED, COVERED, OR | | BARE SOLID COPPER CONDUCTOR NOT SMALLER THAN 8 AWG OR | | BY USING BRASS OR OTHER CORROSION-RESISTANT METAL | | CONDUIT. SEE EXHIBIT 680.11. CONNECTIONS ARE REQUIRED | | TO BE MADE BY EXOTHERMIC WELDS OR BY LISTED PRESSURE | | CONNECTORS, CLAMPS, OR OTHER LISTED MEANS, IN | | ACCORDANCE WITH 250.8. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|