Plan Review Notes For Permit 07040115 |
Permit Number |
07040115 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-06-15 14:50:18 | REVISIONS TO SHEETS 1 AND 2 ARE DENIED | | | | 1) MOST OF THE CHANGES THAT WERE MADE ARE NOT | | IDENTIFIED BY CLOUDING AND NUMBERING. SEE RED MARKS ON | | THE RETURNED PLAN. | | | | 2) ON SHEET 1 THE ELEVATION TO THE TOP OF THE BOND BEAM | | WAS CHANGED TO 9'-0" IN TWO PLACES AND LEFT AT 9'-5" IN | | THE OTHER TWO. PLEASE CORRECT. | | | | 3) SPECIFY THE FL NUMBERS FOR THE LINTELS AND TRUSS | | ANCHORS ON THE PLANS. | | | | 4) ON SHEET 2 THE WRONG CODE SECTION IS SPECIFIED FOR | | NUMBER 1 UNDER PRE-ENGINEERED WOOD TRUSSES. IT SHOULD | | BE R 802.1.6. | | | | 5) THE UPLIFT AND ANCHOR SPECIFIED FOR THE GIRDER TRUSS | | IS NOT ADEQUATE. SEE COMMENTS FOR TRUSS DRAWING | | SUBMITTALS. | | | | IN ORDER TO SPEED PLAN REVIEW, PLEASE RETURN THE DENIED | | REVISED PAGES THAT WERE REDLINED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|