Plan Review Notes
Plan Review Notes For Permit 07040115
Permit Number 07040115
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-15 11:20:14TRUSS LAYOUT AND DRAWINGS IS DENIED
  
 1) THE TRUSS LAYOUT IS REQUIRED TO BE SIGNED AND SEALED
 BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THE STRUCTURE.
 FAC 61G-15-23.002 AND FS471.
  
 2) THE TRUSS DRAWING COVER SHEET IS REQUIRED TO BE
 SIGNED BY THE TRUSS ENGINEER. A SIGNATURE STAMP IS NOT
 ACCEPTABLE. FAC 61G-15-23.002 AND FS471.
  
 3) THE UPLIFT FOR THE 2 PLY GIRDER (A05)TRUSS IS -2366
 PSF WHICH EXCEEDS THE CAPACITY OF THE HETAL 20
 SPECIFIED ON THE PLANS. SUBMIT REVISED ROOF FRAMING
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  