Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2008-05-19 12:43:34*****DENIED*****
  
 * THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEWS STILL NEED TO BE ADDRESSED:
  
  
 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL AS CLASS A, CLASS B, OR CLASS C FOR EXITS,
 EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS.PLEASE
 ADDRESS ON THE APPROPIATE PLAN SHEET
  
 * NEW COMMENTS
  
 C.PROVIDE A LAYOUT OF THE SPRINKLER SYSTEM FOR
 STRUCTURE.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER INSTALLATION
 AND/OR REMODEL.
  
 D. DOES THE STRUCTURE HAVE OR WILL HAVE A FIRE ALARM
 SYSTEM.IF SO, PROVIDE A LAYOUT OF THE FIRE ALARM
 SYSTEM.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR ITS INSTALLATION AND/OR
 REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW