Date |
Text |
2007-09-19 17:36:55 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| |
| 1. OK |
| |
| 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE |
| SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON |
| THE FLOOR PLAN. |
| ****DRINKING FOUNTAIN NOTED, BUT NO SERVICE SINK |
| INDICATED. |
| |
| 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED. |
| SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL |
| PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS |
| FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE |
| FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS |
| WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING |
| PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING |
| THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE |
| ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE |
| SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 & |
| 1107 AS WELL AS TABLE 1106.3. |
| ****ROOF PLAN INDICATED ON SHT 5.1. THE LOCATION OF THE |
| SECONDARY ROOF DRAINS ARE NOT INDICATED. PLEASE SHOW |
| THE LOCATION OF ALL SECONDARY ROOF DRAINS. CALCULATIONS |
| INDICATE 6 RWL'S, BUT ROOF PLAN ONLY SHOWS 4. IF THERE |
| ARE ONLY 4 RD'S THEN 4" RD'S AND PIPING WILL BE |
| REQUIRED PER TABLE 1106.3. PLEASE CLARIFY. INDICATE THE |
| SLOPE OF THE ROOF TO THE ROOF DRAINS. THE EXISTING |
| CONCRETE PASS THROUGH ROOF APPEARS TO BE ABOVE THE TWO |
| STORY SECTION OF THE BUILDING. PLEASE INDICATE IF ANY |
| OF THIS ROOF DRAINS ON TO THE ROOF BELOW. ALSO INDICATE |
| THE HEIGHT & WIDTH DIMENSIONS OF THE VERTICAL WALL |
| ADJACENT TO THE LOWER ROOF ATTACHED TO THE PASS THROUGH |
| ROOF. 1/2 THE AREA OF THIS WALL SHALL BE ADDED TO THE |
| CALCULATIONS ALONG WITH THE PARAPET WALLS. |
| |
| 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN |
| SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL |
| SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS |
| FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| ****DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING HAS NOT BEEN ADDRESSED. |
| |
| 5. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOW: |
| ___FOR THE W/C: |
| A. 11-4.16.5 FLUSH CONTROLS |
| ****DETAIL SHOWS THE FLUSH CONTROLS ON THE WRONG SIDE |
| OF THE TANK. |
| ___FOR THE LAV: |
| A. OK |
| |
| 6. OK |
| 7. OK - (DELETED) |
| 8. OK |
| |
| **********NEW COMMENT********** |
| |
| 1B. SHT 6.1 THE SANITARY PLUMBING ISOMETRIC RISER |
| DIAGRAM DOES NOT MEET CODE REQUIREMENTS FOR SECTION |
| 901.2.1. A VENT IS REQUIRED FOR THE DRINKING FOUNTAIN. |
| ALSO HORIZONTAL DRY VENTS ARE NOT APPROVED PER SECTIONS |
| 905.3 & 905.4. THE VENTS BETWEEN THE LAVS ARE NOT |
| REQUIRED AND ARE HORIZONTAL DRY VENTS. DELETE FROM |
| FLOOR PLAN AND RISER DIAGRAM. VENT AT EACH LAV WILL BE |
| SUFFICIENT. |
| |
| 2B. FLORIDA ENERGY CALCULATIONS INDICATE NO WATER |
| HEATER, BUT THE FLOOR PLAN AND THE RISER DIAGRAM SHOW A |
| WATER HEATER. PLEASE CORRELATE THE INFORMATION ON THE |
| ENERGY CALCULATIONS WITH THE FLOOR PLAN. SECTION |
| 13-103. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |