Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-19 17:36:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. OK
  
 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON
 THE FLOOR PLAN.
 ****DRINKING FOUNTAIN NOTED, BUT NO SERVICE SINK
 INDICATED.
  
 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED.
 SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL
 PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS
 FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS
 WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING
 THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE
 ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE
 SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 &
 1107 AS WELL AS TABLE 1106.3.
 ****ROOF PLAN INDICATED ON SHT 5.1. THE LOCATION OF THE
 SECONDARY ROOF DRAINS ARE NOT INDICATED. PLEASE SHOW
 THE LOCATION OF ALL SECONDARY ROOF DRAINS. CALCULATIONS
 INDICATE 6 RWL'S, BUT ROOF PLAN ONLY SHOWS 4. IF THERE
 ARE ONLY 4 RD'S THEN 4" RD'S AND PIPING WILL BE
 REQUIRED PER TABLE 1106.3. PLEASE CLARIFY. INDICATE THE
 SLOPE OF THE ROOF TO THE ROOF DRAINS. THE EXISTING
 CONCRETE PASS THROUGH ROOF APPEARS TO BE ABOVE THE TWO
 STORY SECTION OF THE BUILDING. PLEASE INDICATE IF ANY
 OF THIS ROOF DRAINS ON TO THE ROOF BELOW. ALSO INDICATE
 THE HEIGHT & WIDTH DIMENSIONS OF THE VERTICAL WALL
 ADJACENT TO THE LOWER ROOF ATTACHED TO THE PASS THROUGH
 ROOF. 1/2 THE AREA OF THIS WALL SHALL BE ADDED TO THE
 CALCULATIONS ALONG WITH THE PARAPET WALLS.
  
 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING HAS NOT BEEN ADDRESSED.
  
 5. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOW:
 ___FOR THE W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ****DETAIL SHOWS THE FLUSH CONTROLS ON THE WRONG SIDE
 OF THE TANK.
 ___FOR THE LAV:
 A. OK
  
 6. OK
 7. OK - (DELETED)
 8. OK
  
 **********NEW COMMENT**********
  
 1B. SHT 6.1 THE SANITARY PLUMBING ISOMETRIC RISER
 DIAGRAM DOES NOT MEET CODE REQUIREMENTS FOR SECTION
 901.2.1. A VENT IS REQUIRED FOR THE DRINKING FOUNTAIN.
 ALSO HORIZONTAL DRY VENTS ARE NOT APPROVED PER SECTIONS
 905.3 & 905.4. THE VENTS BETWEEN THE LAVS ARE NOT
 REQUIRED AND ARE HORIZONTAL DRY VENTS. DELETE FROM
 FLOOR PLAN AND RISER DIAGRAM. VENT AT EACH LAV WILL BE
 SUFFICIENT.
  
 2B. FLORIDA ENERGY CALCULATIONS INDICATE NO WATER
 HEATER, BUT THE FLOOR PLAN AND THE RISER DIAGRAM SHOW A
 WATER HEATER. PLEASE CORRELATE THE INFORMATION ON THE
 ENERGY CALCULATIONS WITH THE FLOOR PLAN. SECTION
 13-103.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]