2007-09-25 10:46:41 | *****DENIED***** |
| |
| * THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| |
| 4.THE DEMOLITION AND/OR THE STOCKING OF NEW BUILDING |
| MATERIALS & SUPPLIES SHALL NOT INTERFERE WITH EMERGENCY |
| RESPONSE ACCESS TO THE PROPERTY OR THE VICINITY THEREOF |
| (INCLUDING STREETS, ALLEYS, FIRE LANES).AMEND |
| SPELLING TO READ FIRE LANES, NOT FINE LINES AS |
| INDICATED ON SHEET 2.1 |
| |
| 5.PLEASE DECLARE THE OCCUPANCY CLASSIFICATION FOR |
| THIS/THESE STRUCTURE(S).NOT SHOWN IN THE PROJECT DATA |
| ON SHEET 2.1 |
| |
| 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| MATERIAL AS CLASS A, CLASS B, OR CLASS C FOR EXITS, |
| EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS.PLEASE |
| ADDRESS ON THE APPROPIATE PLAN SHEET |
| |
| * NEW COMMENTS |
| |
| A.DECLARE WHAT IS TO BE STORED IN THE NEW STORAGE |
| STRUCTURE AND ITS HAZARD CONTENTS IN TERMS OF LOW, |
| MODERATE, OR HIGH. |
| |
| B.NO EMERGENCY LIGHTS NOTED IN THE NEW STORAGE |
| STRUCTURE.PLEASE EXPLAIN OR AMEND. |
| |
| C.PROVIDE A LAYOUT OF THE SPRINKLER SYSTEM FOR |
| STRUCTURE.PLEASE BE ADVISED THAT SEPARATE PLANS AND |
| PERMIT WILL BE REQUIRED FOR SPRINKLER INSTALLATION |
| AND/OR REMODEL. |
| |
| D. DOES THE STRUCTURE HAVE OR WILL HAVE A FIRE ALARM |
| SYSTEM.IF SO, PROVIDE A LAYOUT OF THE FIRE ALARM |
| SYSTEM.PLEASE BE ADVISED THAT SEPARATE PLANS AND |
| PERMIT WILL BE REQUIRED FOR ITS INSTALLATION AND/OR |
| REMODEL. |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |