Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-09-25 10:46:41*****DENIED*****
  
 * THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 4.THE DEMOLITION AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE WITH EMERGENCY
 RESPONSE ACCESS TO THE PROPERTY OR THE VICINITY THEREOF
 (INCLUDING STREETS, ALLEYS, FIRE LANES).AMEND
 SPELLING TO READ FIRE LANES, NOT FINE LINES AS
 INDICATED ON SHEET 2.1
  
 5.PLEASE DECLARE THE OCCUPANCY CLASSIFICATION FOR
 THIS/THESE STRUCTURE(S).NOT SHOWN IN THE PROJECT DATA
 ON SHEET 2.1
  
 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL AS CLASS A, CLASS B, OR CLASS C FOR EXITS,
 EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS.PLEASE
 ADDRESS ON THE APPROPIATE PLAN SHEET
  
 * NEW COMMENTS
  
 A.DECLARE WHAT IS TO BE STORED IN THE NEW STORAGE
 STRUCTURE AND ITS HAZARD CONTENTS IN TERMS OF LOW,
 MODERATE, OR HIGH.
  
 B.NO EMERGENCY LIGHTS NOTED IN THE NEW STORAGE
 STRUCTURE.PLEASE EXPLAIN OR AMEND.
  
 C.PROVIDE A LAYOUT OF THE SPRINKLER SYSTEM FOR
 STRUCTURE.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER INSTALLATION
 AND/OR REMODEL.
  
 D. DOES THE STRUCTURE HAVE OR WILL HAVE A FIRE ALARM
 SYSTEM.IF SO, PROVIDE A LAYOUT OF THE FIRE ALARM
 SYSTEM.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR ITS INSTALLATION AND/OR
 REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722