Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-29 19:51:552007-08-29 19:51:55
  
 ** DENIED2ND REVIEW**
  
 1) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTE #2 WHICH
 SPECIFICALLY GAVE A *HEADS-UP* ON THE ENERGY
 CALCULATIONS.
 PLEASE BE SURE WHEN SUBMITTING THE INPUT DATA REPORT
 THAT THE INFORMATION SHOWN ON THIS REPORT COORDINATES
 WITH THE NUMBER OF FIXTURES ON PLANS, THE TOTAL WATTAGE
 OF EACH FIXTURE AND THE METHOD FO CONTROLS.
 PLEASE SEE THE LUMINARIES SHOWN ON THE PLANS DO NOT
 MATCH WITH THE IDR.
 PLEASE SEE THE TYPE OF INPUT FOR *HOTEL/MOTEL* WHICH IS
 NOT POSSIBLE.
 PLEASE SEE THE METHOD OF CONTROLS IS BEING SHOWN AS
 *MANUAL ON/OFF* ON THE INPUT DATA REPORT HOWEVER
 AUTOMATE CONTROLS ARE SHOWN ON PLANS. PLEASE COORDINATE
 PLANS WITH THE CALCULATIONS.
 PLEASE ALSO SEE THE NEW REVISED ENERGY CALCULATIONS
 WHICH ARE NOT SIGNED, DATED AND SEALED AS REQUIRED PER
 FBC 13-103.1.1.1, FS 471.025, FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING LIGHT FIXTURE WHICH IS
 REDLINED ON PLANS.
 FBC 106.1.2
  
 3) NOTE: PLEASE INDICATE LOAD ON THE EXISTING GUTTER
 FOR ADDING NEW LOADS.
 NEC 220
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE NO CONDUCTORS ARE BEING SHOWN FROM
 GUTTER TO NEW MAIN.
 230, 310.16, 240.4, ETC
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE SEE MISSING NEUTRAL TO THE MEANS OF
 DISCONNECT AT THE DETACHED BUILDING.
 250.32
 EVEN AS A NEUTRAL IS NOT NEEDED FROM THE MAIN AT THE
 DETACHED BUILDING TO THE TRANSFORMER FOR THE SEPARATELY
 DERIVED SYSTEM, A NEUTRAL IS STILL REQUIRED TO THE
 MAIN.
 PLEASE SEE MISSING COLD WATER PIPE AT THE DETACHED
 STRUCTURE PER 250.50
 PLEASE VERIFY THE GROUNDING ELECTRODE FOR THE
 TRANSFORMER PER 250.58.
  
 AS STATED ON THE PREVIOUS REVIEW:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]