Date |
Text |
2007-08-29 19:51:55 | 2007-08-29 19:51:55 |
| |
| ** DENIED2ND REVIEW** |
| |
| 1) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTE #2 WHICH |
| SPECIFICALLY GAVE A *HEADS-UP* ON THE ENERGY |
| CALCULATIONS. |
| PLEASE BE SURE WHEN SUBMITTING THE INPUT DATA REPORT |
| THAT THE INFORMATION SHOWN ON THIS REPORT COORDINATES |
| WITH THE NUMBER OF FIXTURES ON PLANS, THE TOTAL WATTAGE |
| OF EACH FIXTURE AND THE METHOD FO CONTROLS. |
| PLEASE SEE THE LUMINARIES SHOWN ON THE PLANS DO NOT |
| MATCH WITH THE IDR. |
| PLEASE SEE THE TYPE OF INPUT FOR *HOTEL/MOTEL* WHICH IS |
| NOT POSSIBLE. |
| PLEASE SEE THE METHOD OF CONTROLS IS BEING SHOWN AS |
| *MANUAL ON/OFF* ON THE INPUT DATA REPORT HOWEVER |
| AUTOMATE CONTROLS ARE SHOWN ON PLANS. PLEASE COORDINATE |
| PLANS WITH THE CALCULATIONS. |
| PLEASE ALSO SEE THE NEW REVISED ENERGY CALCULATIONS |
| WHICH ARE NOT SIGNED, DATED AND SEALED AS REQUIRED PER |
| FBC 13-103.1.1.1, FS 471.025, FAC 61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE MISSING LIGHT FIXTURE WHICH IS |
| REDLINED ON PLANS. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE INDICATE LOAD ON THE EXISTING GUTTER |
| FOR ADDING NEW LOADS. |
| NEC 220 |
| FBC 106.3.5.1.2 |
| |
| 4) NOTE: PLEASE SEE NO CONDUCTORS ARE BEING SHOWN FROM |
| GUTTER TO NEW MAIN. |
| 230, 310.16, 240.4, ETC |
| FBC 106.3.5.1.2 |
| |
| 5) NOTE: PLEASE SEE MISSING NEUTRAL TO THE MEANS OF |
| DISCONNECT AT THE DETACHED BUILDING. |
| 250.32 |
| EVEN AS A NEUTRAL IS NOT NEEDED FROM THE MAIN AT THE |
| DETACHED BUILDING TO THE TRANSFORMER FOR THE SEPARATELY |
| DERIVED SYSTEM, A NEUTRAL IS STILL REQUIRED TO THE |
| MAIN. |
| PLEASE SEE MISSING COLD WATER PIPE AT THE DETACHED |
| STRUCTURE PER 250.50 |
| PLEASE VERIFY THE GROUNDING ELECTRODE FOR THE |
| TRANSFORMER PER 250.58. |
| |
| AS STATED ON THE PREVIOUS REVIEW: |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |