Plan Review Notes For Permit 07040094 |
Permit Number |
07040094 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-30 16:31:55 | *****DENIED***** | | | | | | 1.PROVIDE A SITE PLAN WHICH WOULD RELAY THE LOCATION | | OF BUILDING TO SURROUNDING STREETS, ROADS, ETC | | | | 2.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL | | BE REFERENCED. | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 4.THE DEMOLITION AND/OR THE STOCKING OF NEW BUILDING | | MATERIALS & SUPPLIES SHALL NOT INTERFERE WITH EMERGENCY | | RESPONSE ACCESS TO THE PROPERTY OR THE VICINITY THEREOF | | (INCLUDING STREETS, ALLEYS, FIRE LANES). | | | | 5.PLEASE DECLARE THE OCCUPANCY CLASSIFICATION FOR | | THIS/THESE STRUCTURE(S). | | | | 6.PLEASE PROVIDE OCCUPANT LOAD/EGRESS REQUIREMENTS | | | | 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | MATERIAL AS CLASS A, CLASS B, OR CLASS C FOR EXITS, | | EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|