Plan Review Notes
Plan Review Notes For Permit 07040088
Permit Number 07040088
Review Stop B
Sequence Number 4
Notes
Date Text
2007-07-30 10:03:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 COMMENT FROM PREVIOUS LIST:
  
 1.)THE SPAN SHOULD BE LARGER THAN THE OPENING HEIGHT.
 SPAN IS BLADE LENGTH.THIS MAY AFFECT ANCHOR SPACING
 FOR SOME OPENINGS.PLEASE REVISE SPANS AND CONFIRM
 ANCHOR SPACING.
  
 4TH REVIEW - THE SPANS ARE NOW SMALLER THAN THE OPENING
 HEIGHT.THIS MAY BE THE CASE FOR AN INSIDE (TRAPPED)
 MOUNT, BUT NOT FOR A WALL MOUNT.YOU HAVE WRITTEN TWO
 NOTES ON THE INSTALLATION SCHEDULE.ONE STATES "ANCHOR
 SPACING IS FINE."PLEASE SEE OPENING 7.WITH A HEIGHT
 OF 100", WHEN YOU ADD THE 1 1/2 TO THE TOP AND BOTTOM
 OF THE OPENING FOR A WALL MOUNT, THE SPAN IS 103", OR
 8'7", REQUIRING USE OF THE 9' SPAN CHART RATHER THAN
 THE 8' SPAN CHART AS WOULD BE REQUIRED FOR THE 96" SPAN
 YOU HAVE SPECIFIED.THIS DOES NOT AFFECT THE TOP MOUNT
 BUT DOES AFFECT ANCHOR SPACING FOR THE BOTTOM.
  
 THE SECOND NOTE STATES "WHAT ELSE KNOW?"IF YOU NEED
 ASSISTANCE, OR DO NOT UNDERSTAND THE CORRECTIONS,
 PLEASE HAVE THE QUALIFIER SCHEDULE A MEETING.
  
 NEW COMMENT:
  
 2.)TWO COMPLETE COLLATED IDENTICAL SETS REQUIRED FOR
 PERMITTING.ONLY ONE NEW INSTALLATION SCHEDULE WAS
 SUBMITTED.IF THIS WAS THE ONLY COMMENT, I WOULD HAVE
 PRINTED THIS FOR YOU.HOWEVER, DUE TO WORKLOAD, I AM
 GENERALLY NOT ABLE TO PROVIDE COPIES AT THIS TIME.
  