2007-04-21 12:53:27 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.)OPENING REFERENCED IN PREVIOUS LIST WAS NOT |
| REVISED. |
| |
| 2.)THIS IS EXPOSURE C.YOU HVE DESIGNED TO 47.2 |
| EXPOSURE B WORST CASE.THIS IS NOT HIGH ENOUGH FOR |
| SOME OPENINGS, SUCH AS SOME ON THE END ZONES SUCH AS |
| OPENING 5.WORST CASE FOR EXPOSURE C, 15' MRH, IS |
| -57.1.OPENING 5 WOULD REQUIRE 9" SPACING, NOT 12". |
| |
| 3.) OPENING 4 REQUIRES USE OF THE 15' CHART, HAS A |
| MINIMUM REQUIRED DESIGN PRESSURE OF -48.19, SO YOU MUST |
| USE THE -77PSF CHART.THIS REQUIERS 4" SPACING, NOT |
| 12". |
| |
| 4.)SOME OF THE OPENING SIZES DO NOT ALL CORRELATE |
| WITH THE FLOOR PLAN; FOR INSTANCE, SEE OPENING 18.ONE |
| STATES 26X57, ONE IS 26X50. |
| |
| 5.)CHECK ALL OPENINGS.OTHER OPENINGS MAY HAVE |
| INCORRECT ANCHOR SPACING. |
| |
| 6.)THERE ARE TWO DIFFERENT FLORIDA STATE PRODUCT |
| APPROVALS INCLUDED IN THE PACKAGE, ONE EVALUATION |
| REPORT.INCLUDE ONLY THE FL STATE PA THAT APPLIES TO |
| THIS JOB. |
| |