2007-04-21 12:53:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)OPENING REFERENCED IN PREVIOUS LIST WAS NOT
 REVISED.
  
 2.)THIS IS EXPOSURE C.YOU HVE DESIGNED TO 47.2
 EXPOSURE B WORST CASE.THIS IS NOT HIGH ENOUGH FOR
 SOME OPENINGS, SUCH AS SOME ON THE END ZONES SUCH AS
 OPENING 5.WORST CASE FOR EXPOSURE C, 15' MRH, IS
 -57.1.OPENING 5 WOULD REQUIRE 9" SPACING, NOT 12".
  
 3.) OPENING 4 REQUIRES USE OF THE 15' CHART, HAS A
 MINIMUM REQUIRED DESIGN PRESSURE OF -48.19, SO YOU MUST
 USE THE -77PSF CHART.THIS REQUIERS 4" SPACING, NOT
 12".
  
 4.)SOME OF THE OPENING SIZES DO NOT ALL CORRELATE
 WITH THE FLOOR PLAN; FOR INSTANCE, SEE OPENING 18.ONE
 STATES 26X57, ONE IS 26X50.
  
 5.)CHECK ALL OPENINGS.OTHER OPENINGS MAY HAVE
 INCORRECT ANCHOR SPACING.
  
 6.)THERE ARE TWO DIFFERENT FLORIDA STATE PRODUCT
 APPROVALS INCLUDED IN THE PACKAGE, ONE EVALUATION
 REPORT.INCLUDE ONLY THE FL STATE PA THAT APPLIES TO
 THIS JOB.
  