Notes
Date Text
2007-04-12 10:09:39 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER
 INFORMATION REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE.
  
 2} THERE IS A NOTE ON THE PLAN THAT THE EXISTING FIRE
 PUMP DISCONNECT IS TO BE DEMOLISHED. PLEASE EXPOUND ON
 THIS COMMENT IF IT IS WITHIN THE SCOPE OF THIS PERMIT.
 IF IT IS NOT, PLEASE REMOVE, AND SUBMIT PLANS WITH
 INFORMATION PERTINENT TO THE SCOPE.
  
 3} PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE
 NOT ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE
 BY THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481,
 AS APPLICABLE.
  
 4}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES OR EQUUIPMENT BEING INSTALLED UNDER THIS
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  