Plan Review Notes
Plan Review Notes For Permit 07040028
Permit Number 07040028
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-06 07:27:46DENIED;
 1. PROJECT DISCRIPTION ON PERMIT APPLICATION IS NOT THE
 SAME AS PLANS SHOW. APPLICATION STATES LAUNDRY ROOMS ON
 1 -2 & 5 TH FLOORS. PAGE A-1 PLUMBING RISER
 DIAGRAMSHOWS LAUNDRY ROOMS ON 2ND THRU 6 TH FLOORS.
 PLEASE CORRECT.
 2.SHOW THE NUMBER OF DWELLING UNITS, ON PLANS, AND
 THE NUMBER OF WASHING MACHINES. MUST COMPLY
 WITHFBC-2004 PLUMBING TABLE 403.1 R2.
 3. SECTION 412 REQUIRES FLOOR DRAINS FOR CENTRAL
 WASHING FACILITIES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695