2007-04-17 12:27:08*** DENIED ***
 1) SEE PLANS PAGE A2 STATES, EXISTING VENTS FOR DRYERS
 TO BE REUSED. CONNECT TO NEW DRYERS. "DRYER VENT CAN
 ONLY MAKE (3) TURNS OF 90 DEGREES AND BE UNDER 10'-0"
 FROM UNIT TO VENT". SEE 2004 FBC/M 504.6 AND 504.7
 CLOTHES DRYER TRANSITION DUCTS USED TO CONNECT THE
 APPLIANCE TO THE EXHAUST DUCT SYSTEM SHALL BE LIMITED
 TO SINGLE LENGTHS NOT TO EXCEED 8 FEET (2438 MM) IN
 LENGTH AND SHALL BE LISTED AND LABELED FOR THE
 APPLICATION. TRANSITION DUCTS SHALL NOT BE CONCEALED
 WITHIN CONSTRUCTION, PLEASE CORRECT ON PLANS.
  
 2) IF LENGTHENING THE CLOTHES DRYER VENT PLEASE SEE
 2004 FBC/M 504 AND ADD DETAIL TO PLANS.
  
 3) IF CLOTHES DRYER VENT IS TO EXCEED THE 2004 FBC/M
 504 MAXIMUM LENGTH, PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR THE CLOTHES DRYER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729. .