Plan Review Notes For Permit 07040028 |
Permit Number |
07040028 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-04-17 12:27:08 | *** DENIED *** | | 1) SEE PLANS PAGE A2 STATES, EXISTING VENTS FOR DRYERS | | TO BE REUSED. CONNECT TO NEW DRYERS. "DRYER VENT CAN | | ONLY MAKE (3) TURNS OF 90 DEGREES AND BE UNDER 10'-0" | | FROM UNIT TO VENT". SEE 2004 FBC/M 504.6 AND 504.7 | | CLOTHES DRYER TRANSITION DUCTS USED TO CONNECT THE | | APPLIANCE TO THE EXHAUST DUCT SYSTEM SHALL BE LIMITED | | TO SINGLE LENGTHS NOT TO EXCEED 8 FEET (2438 MM) IN | | LENGTH AND SHALL BE LISTED AND LABELED FOR THE | | APPLICATION. TRANSITION DUCTS SHALL NOT BE CONCEALED | | WITHIN CONSTRUCTION, PLEASE CORRECT ON PLANS. | | | | 2) IF LENGTHENING THE CLOTHES DRYER VENT PLEASE SEE | | 2004 FBC/M 504 AND ADD DETAIL TO PLANS. | | | | 3) IF CLOTHES DRYER VENT IS TO EXCEED THE 2004 FBC/M | | 504 MAXIMUM LENGTH, PLEASE SUBMIT DETAILED | | MANUFACTURER'S SPECIFICATION'S AND INSTALLATION | | INSTRUCTIONS FOR THE CLOTHES DRYER. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. . |
|