2007-04-16 16:14:06 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. MORE INFORMATION IS REQUIRED. PLEASE SUBMIT A FLOOR |
| PLAN THAT INDICATES THE EXISTING PLUMBING LAYOUT AND |
| PLEASE ADHERE TO THE FOLLOWING. |
| |
| A} IF PLUMBING LAYOUT IS THE SAME |
| WITH NO CHANGES, PLEASE INDICATE THIS ON |
| THE DRAWING. |
| B} IF PLUMBING LAYOUT IS THE |
| SAME AND THE PLUMBING FIXTURES ARE TO BE |
| CHANGED, PLEASE INDCATE ON THE DRAWING. |
| "EXACT FIXTURE CHANGE OUT ONLY." |
| C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT |
| FROM THE EXISTING PLEASE SUBMIT A FLOOR PLAN INDICATING |
| THE NEW PROPOSED PLUMBING LAYOUT ANDFOLLOW WHAT IS |
| REQUIRED IN COMMENT #2. |
| |
| 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 |
| PLUMBING PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC |
| RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND |
| SIZES WITH CLEANOUT LOCATIONS. WATER SUPPLY PIPING |
| RISER DIAGRAM WITH SIZES, TIE IN LOCATION, BACKFLOW |
| LOCATION, SHUT OFF VALVES. |
| NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| DOES NOT CLEARLY INDICATE WHAT PLUMBING IS EXISTING AND |
| WHAT IS NEW. PLEASE CLARIFY ON THE RESUBMITTAL. |
| |
| 3. PLEASE CLARIFY WHAT A "STUDENT VENT" IS ON THE |
| RESUBMITTAL. I THINK YOU MEAN THAT IT IS AN AIR |
| ADMITTANCE VALVE (A.A.V.) PER FBC-2004 PLUMBING, |
| SECTION 917, MANUFACTURED BY"STUDER VENT". |
| |
| 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |