2008-02-20 13:32:19 | RESIDENTIAL ADDITION BUILDING REVIEW SIXTH CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2006 REVISIONS. |
| |
| 1- FLAT ROOFASSEMBLY NAIL ENHANCING SPACING AT |
| PERIMETER AND CORNER AREAS SHOWN ON SHEET A1 ARE |
| EXACTLY THE SAMEAS SHOWN ON NOA 03-0501.05.ENGINEER |
| IS NOT PROVIDING ANY NAIL ENHANCING ON THE CONTRARY IS |
| PROVIDING THE SAME SPECIFICATIONS THAT ARE SHOWN ON THE |
| PRODUCT APPROVAL ON SHEET 18 OF 21.ENGINEER TO READ |
| HOW TO DO THE RAS 117 CALCULATIONS AS REQUIRED BY |
| GENERAL LIMITATION #7 OF NOA SUBMITTED AND PROVIDE SUCH |
| CALCULATIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| TO VERIFY COMPLIANCE WITH TABLE R301.2(2) OF 2004 |
| FLORIDA RESIDENTIAL CODE. |
| |
| ***NOTE: ONE SET OF PLANS WILL BE RETAINED IN THIS |
| OFFICE TO BE SEND TO THE BOARD OF ENGINEER'S FOR |
| REVIEW. |
| |
| 2- PLANS SUBMITTED NOW ARE REVISED FROM THOSE SUBMITTED |
| ON EARLIER RE-SUBMITTALS. NOW ALL THE AREA CALCULATIONS |
| DON'T MATCH ACTUAL AREAS SHOWN ON PLANS AND DON'T ADD |
| UP CORRECTLY.REVISE AS REQUIRED. PERMIT FEES AND |
| RADON FEES WILL BE ADJUSTED ACCORDINGLY ONCE THE AREA |
| CALCULATIONS ARE CORRECTED. |
| |
| 3- NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS IF WORK |
| IS NOT STARTED.NEED RE-RECORDED NOC AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |