Plan Review Notes For Permit 07031080 |
Permit Number |
07031080 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-11-26 09:07:16 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM600C-04R, | | "R", SEE 2004 FBC 13-600.3.C (12-8-06 REVISION). | | | | 2) ENERGY CALCULATIONS LINE 9A-1 IS CALLING FOR R 4.2 | | INSULATION, SEE TABLE 6C-1 ON THE SECOND PAGE OF THE | | ENERGY CALCULATIONS SUBMITTED STATES THE "MINIMUM" | | INSULATION IS TO BE R-5, SEE 2004 FBC 13-602.1.C.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|