Plan Review Notes For Permit 07031080 |
Permit Number |
07031080 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-12-12 13:46:00 | RESIDENTIAL ADDITION BUILDING REVIEW FIFTH CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2006 REVISIONS. | | | | 1- ENERGY CALCULATIONS:R VALUES SHOWN FOR ROOF AND | | WALLS ON ENERGY CALCULATIONS DON'T MATCH THOSE SHOWN ON | | PLANS.REVISE AS REQUIRED TO MATCH. | | ALSO, SEE MECHANICAL PLAN REVIEWER COMMENTS AND | | COORDINATE AS REQUIRED. | | ACCORDING TO TABLE 6C-1 THE MINIMUM WALL INSULATION IS | | R-5. THEN, WHY INSTALLING R-4.2?. REVISE AS REQUIRED. | | | | 2- DIMENSIONS SHOWN ON SURVEY DON'T MATCH DIMENSIONS | | SHOWN ON PLANS. REVISE AS REQUIRED.(REPEAT COMMENT). | | | | 3- FLAT ROOF PRODUCT APPROVAL: | | A) CLEARLY SPECIFY ON SELECTED ASSEMBLY , PAGE 18, | | THE SPECIFIC FASTENING OPTION FOR BASE SHEET TO BE USED | | TO VERIFY COMPLIANCE WITH THE UPLIFT DESIGN PRESSURES. | | (REPEAT COMMENT). | | | | B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING | | AT PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION | | #7 ON LAST PAGE OF NOA SUBMITTED. (REPEAT COMMENT). | | | | 4- ROOF FRAMING PLAN: REVISE NUMBER OF NAILS TO BE USED | | FOR SIMPSON MTSM20. SEE CURRENT CATALOG AND REVISE AS | | REQUIRED. OTHERWISE, PROVIDE COMPLETE ENGINEERINGFOR | | NAIL FASTENERS THAT DIFFER FROM THOSE TESTED AND | | PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|