Plan Review Notes
Plan Review Notes For Permit 07031080
Permit Number 07031080
Review Stop B
Sequence Number 4
Notes
Date Text
2007-10-02 15:15:00RESIDENTIAL ADDITION BUILDING REVIEW FOURTH CHECKLIST.
  
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004.
  
 1- ENERGY CALCULATIONS (FIRST TIME ENERGY CALCS ARE
 SUBMITTED):
 A) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF
 FORM.
 B) JURISDICTION NUMBER ON TOP OF FORM IS INCORRECT.
 REVISE AS REQUIRED.
 C) COMPLETE ALL INFORMATION ON TOP OF FORM,
 INCLUDING NAME OF BUILDER AND PERMITTING OFFICE.
 D) CLARIFY WHY THE CONDITIONED FLOOR AREA ON ITEM #4
 IS 210SF, WHILEUNDER ATTIC SQUARE FOOTAGE ON ITEM
 #10(A) IS 274SF. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 E) COMPLETE INFORMATION ON TABLE 6C-1.
 F) INFORMATION ON TABLE 6C-2 IS WRONG. REVISE AS
 REQUIRED.
  
 2- ROOF FRAMING PLAN: REVISE NUMBER OF FASTENERS
 SPECIFIED FOR SIMPSON HETAL20 CONNECTOR.SEE CURRENT
 SIMPSON CATALOG AND REVISE AS REQUIRED.OTHERWISE
 PROVIDE COMPLETE ENGINEERING ANALYSISFOR NUMBER OF
 FASTENERS THAT DIFFER FROM THOSE TESTED AND PUBLISHED
 BY THE MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 3- ROOF FRAMING PLAN AND EXISTING WALL:NEED TO
 SPECIFY WOOD TO MASONRY CONNECTOR FOR ROOF JOISTS THAT
 ARE RESTING ON EXISTING EXTERIOR WALL.FLOOR PLAN
 SHOWS THIS WALL AS CONCRETE BLOCK WALL WITH FILLED
 CELLS AT DOOR OPENING.CONNECTOR MTS-18IS A WOOD TO
 WOOD CONNECTOR. REVISE INFORMATION ON ROOF FRAMING PLAN
 AS REQUIRED. CLEARLY IDENTIFY WHAT KIND OF WALL IS THE
 EXISTING WALL. IS IT MASONRY OR WOOD FRAMED WALL?. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004. (THIS INFORMATION
 WAS REQUESTED ON PREVIOUS CHECKLIST ALSO).
  
 4- SOFFIT VENTILATION SPECS SHOWN ON WALL STEM DETAIL
 ON SHEET A2 WERE REVISED AGAIN AND STILLDON'T COMPLY
 WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.NEED
 TO PROVIDE CROSS VENTILATION.SEPARATE VENTS DON'T
 PROVIDE CROSS VENTILATION ON A FLAT ROOFWITH 2X12
 ROOF JOISTS. REVISE AS REQUIRED.
  
 5- WALL STEM DETAIL ON SHEET A2: SPECIFICATIONS FOR
 INTERIOR CEILING CONSTRUCTION ARE NOT CLEAR.REVISE
 INFORMATION AS REQUIRED. REMEMBER THIS IS AN INTERIOR
 CEILING. ALSO, WHERE IS THE FIREBLOCKING LOCATED AT?.
 THERE ARE NOT TRUSSES IN THIS ROOF EITHER.WHY USING
 EXTERIOR GRADE GYPSUM BOARD?. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004. REVISE COMPLETE SPECS AS
 REQUIRED.
  
 6- REVISE EMERGENCY EGRESS WINDOWS INFORMATION ON SHEET
 A2:
 A) REVISE REFERENCES. SEC. 1005.4 AND SEC. 105.43
 DON'T CORRESPOND TO 2004 FLORIDA RESIDENTIAL CODE.
 B) NET CLEAR OPENING OF 20". IS THIS FOR CLEAR WIDTH?.
 REVISE AS REQUIRED.
 C) EGRESS IS MEASURED BY EGRESS CLEAR OPENING,NOT
 MINIMUM TOTAL GLASS AREA. REVISE AS REQUIRED.
  
 7- STRUCTURAL LOADS ON SHEET A2:
 A) FLOOR AND ROOF LIVE LOADS CAN'T BE 10PSF.REVISE
 AS REQUIRED.
 B) CLARIFY WHY CEILING DEAD LOAD IS 20LBS?. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 C) CLARIFY WHYSUBMITTING WALL INTERIOR AND
 EXTERIOR DEAD LOADS AND WHERE ARE THESE NUMBERSTAKEN
 FROM. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 D) SPECIFY BUILDING CODE USED AND WIND LOADS AS
 REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
 THESE INFORMATION WAS GIVEN ON PREVIOUS SUBMITTALS, BUT
 NOW IS NOT SHOWN ON PLANS. PROVIDE ALL REQUIRED
 INFORMATION.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) FLAT ROOF ASSEMBLY:
 * NOA 04-0506.03 EXPIRED ON 5-23-07. NEED CURRENT ONE.
  
 ** NOA 04-0506.03 SUBMITTEDHAS NOTHNG TO DO WITH
 FL735.
 *** CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED.
 **** CLEARLY IDENTIFY ASSEMBLY BASE SHEET FASTENING
 OPTION.
 ***** PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7. SEE GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA SUBMITTED. (NOTE: IF GENERAL
 LIMITATION #7 STATES THAT RAS 117 CALCULATIONS MUST BE
 DONE BY A PROFESSIONAL ARCHITECT, ENGINEER OR
 REGISTERED ROOF CONSULTANT, THEN SUCH CALCS MUST BE
 DONE BY ONE OF THEM ONLY).
  
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 USE COMPANY STANDARD REVIEW STAMP OR WRITE ENGINEERS
 NAME AND CLEARLY WRITE REVIEWED AND APPROVED AND SIGNED
 BY WHO DID THE REVIEW. PRODUCT APPROVALS SUBMITTED WERE
 REVIEWED BY SOMEBODY ELSE OTHER THAN THE ENGINEER OF
 RECORD. AND ENGINEER'S SIGNATURE WITHOUT NAME IS NOT
 INFORMATION ADEQUATE ENOUGH TO IDENTIFY PERSON WHO
 REVIEW THE PRODUCT APPROVAL. THESE COMMENT WAS
 ADDRESSED ON SEVERAL OCCASIONS.
  
 10- SURVEY AND FLOOR PLANS DON'T MATCH REVISE
 DIMENSIONS AS REQUIRED TO MATCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- NOTICE OF COMMENCEMENT WAS RECORDED ON 03/30/07.
 NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED.SEC. 713.13 FLORIDA
 STATUTE. NEED RE-RECORDED NOTICE OF COMMENCEMENT.
  
 12- NOW TYPICAL WALL SECTION IS MISSING THE ROOF AND
 WALL INSULATION. PROVIDE COMPLETE SPECIFICATIONS AS
 REQUIRED. SEC. 13-600 FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712