2007-10-02 15:15:00 | RESIDENTIAL ADDITION BUILDING REVIEW FOURTH CHECKLIST. |
| |
| REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| 2004. |
| |
| 1- ENERGY CALCULATIONS (FIRST TIME ENERGY CALCS ARE |
| SUBMITTED): |
| A) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF |
| FORM. |
| B) JURISDICTION NUMBER ON TOP OF FORM IS INCORRECT. |
| REVISE AS REQUIRED. |
| C) COMPLETE ALL INFORMATION ON TOP OF FORM, |
| INCLUDING NAME OF BUILDER AND PERMITTING OFFICE. |
| D) CLARIFY WHY THE CONDITIONED FLOOR AREA ON ITEM #4 |
| IS 210SF, WHILEUNDER ATTIC SQUARE FOOTAGE ON ITEM |
| #10(A) IS 274SF. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| E) COMPLETE INFORMATION ON TABLE 6C-1. |
| F) INFORMATION ON TABLE 6C-2 IS WRONG. REVISE AS |
| REQUIRED. |
| |
| 2- ROOF FRAMING PLAN: REVISE NUMBER OF FASTENERS |
| SPECIFIED FOR SIMPSON HETAL20 CONNECTOR.SEE CURRENT |
| SIMPSON CATALOG AND REVISE AS REQUIRED.OTHERWISE |
| PROVIDE COMPLETE ENGINEERING ANALYSISFOR NUMBER OF |
| FASTENERS THAT DIFFER FROM THOSE TESTED AND PUBLISHED |
| BY THE MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| 3- ROOF FRAMING PLAN AND EXISTING WALL:NEED TO |
| SPECIFY WOOD TO MASONRY CONNECTOR FOR ROOF JOISTS THAT |
| ARE RESTING ON EXISTING EXTERIOR WALL.FLOOR PLAN |
| SHOWS THIS WALL AS CONCRETE BLOCK WALL WITH FILLED |
| CELLS AT DOOR OPENING.CONNECTOR MTS-18IS A WOOD TO |
| WOOD CONNECTOR. REVISE INFORMATION ON ROOF FRAMING PLAN |
| AS REQUIRED. CLEARLY IDENTIFY WHAT KIND OF WALL IS THE |
| EXISTING WALL. IS IT MASONRY OR WOOD FRAMED WALL?. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. (THIS INFORMATION |
| WAS REQUESTED ON PREVIOUS CHECKLIST ALSO). |
| |
| 4- SOFFIT VENTILATION SPECS SHOWN ON WALL STEM DETAIL |
| ON SHEET A2 WERE REVISED AGAIN AND STILLDON'T COMPLY |
| WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.NEED |
| TO PROVIDE CROSS VENTILATION.SEPARATE VENTS DON'T |
| PROVIDE CROSS VENTILATION ON A FLAT ROOFWITH 2X12 |
| ROOF JOISTS. REVISE AS REQUIRED. |
| |
| 5- WALL STEM DETAIL ON SHEET A2: SPECIFICATIONS FOR |
| INTERIOR CEILING CONSTRUCTION ARE NOT CLEAR.REVISE |
| INFORMATION AS REQUIRED. REMEMBER THIS IS AN INTERIOR |
| CEILING. ALSO, WHERE IS THE FIREBLOCKING LOCATED AT?. |
| THERE ARE NOT TRUSSES IN THIS ROOF EITHER.WHY USING |
| EXTERIOR GRADE GYPSUM BOARD?. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. REVISE COMPLETE SPECS AS |
| REQUIRED. |
| |
| 6- REVISE EMERGENCY EGRESS WINDOWS INFORMATION ON SHEET |
| A2: |
| A) REVISE REFERENCES. SEC. 1005.4 AND SEC. 105.43 |
| DON'T CORRESPOND TO 2004 FLORIDA RESIDENTIAL CODE. |
| B) NET CLEAR OPENING OF 20". IS THIS FOR CLEAR WIDTH?. |
| REVISE AS REQUIRED. |
| C) EGRESS IS MEASURED BY EGRESS CLEAR OPENING,NOT |
| MINIMUM TOTAL GLASS AREA. REVISE AS REQUIRED. |
| |
| 7- STRUCTURAL LOADS ON SHEET A2: |
| A) FLOOR AND ROOF LIVE LOADS CAN'T BE 10PSF.REVISE |
| AS REQUIRED. |
| B) CLARIFY WHY CEILING DEAD LOAD IS 20LBS?. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| C) CLARIFY WHYSUBMITTING WALL INTERIOR AND |
| EXTERIOR DEAD LOADS AND WHERE ARE THESE NUMBERSTAKEN |
| FROM. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| D) SPECIFY BUILDING CODE USED AND WIND LOADS AS |
| REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| THESE INFORMATION WAS GIVEN ON PREVIOUS SUBMITTALS, BUT |
| NOW IS NOT SHOWN ON PLANS. PROVIDE ALL REQUIRED |
| INFORMATION. |
| |
| 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| FOR: |
| A) FLAT ROOF ASSEMBLY: |
| * NOA 04-0506.03 EXPIRED ON 5-23-07. NEED CURRENT ONE. |
| |
| ** NOA 04-0506.03 SUBMITTEDHAS NOTHNG TO DO WITH |
| FL735. |
| *** CLEARLY IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE |
| INSTALLED. |
| **** CLEARLY IDENTIFY ASSEMBLY BASE SHEET FASTENING |
| OPTION. |
| ***** PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY |
| GENERAL LIMITATION #7. SEE GENERAL LIMITATION #7 ON |
| LAST PAGE OF NOA SUBMITTED. (NOTE: IF GENERAL |
| LIMITATION #7 STATES THAT RAS 117 CALCULATIONS MUST BE |
| DONE BY A PROFESSIONAL ARCHITECT, ENGINEER OR |
| REGISTERED ROOF CONSULTANT, THEN SUCH CALCS MUST BE |
| DONE BY ONE OF THEM ONLY). |
| |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| USE COMPANY STANDARD REVIEW STAMP OR WRITE ENGINEERS |
| NAME AND CLEARLY WRITE REVIEWED AND APPROVED AND SIGNED |
| BY WHO DID THE REVIEW. PRODUCT APPROVALS SUBMITTED WERE |
| REVIEWED BY SOMEBODY ELSE OTHER THAN THE ENGINEER OF |
| RECORD. AND ENGINEER'S SIGNATURE WITHOUT NAME IS NOT |
| INFORMATION ADEQUATE ENOUGH TO IDENTIFY PERSON WHO |
| REVIEW THE PRODUCT APPROVAL. THESE COMMENT WAS |
| ADDRESSED ON SEVERAL OCCASIONS. |
| |
| 10- SURVEY AND FLOOR PLANS DON'T MATCH REVISE |
| DIMENSIONS AS REQUIRED TO MATCH. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 11- NOTICE OF COMMENCEMENT WAS RECORDED ON 03/30/07. |
| NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF |
| RECORDING IF WORK IS NOT STARTED.SEC. 713.13 FLORIDA |
| STATUTE. NEED RE-RECORDED NOTICE OF COMMENCEMENT. |
| |
| 12- NOW TYPICAL WALL SECTION IS MISSING THE ROOF AND |
| WALL INSULATION. PROVIDE COMPLETE SPECIFICATIONS AS |
| REQUIRED. SEC. 13-600 FBC 2004. |
| |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |