2007-06-15 17:02:06 | BUILDING REVIEW 2ND CHECKLIST: |
| 1- ROOF FRAMING PLAN: |
| A) SPECIFY HOW MANY FASTENERS ARE REQUIRED FOR TRUSS |
| CONNECTORS. INFORMATION IS MISSING. |
| |
| B) ROOF FRAMING PLAN SPECIFIESEXISTING WALL TO BE |
| WOOD FRAMING.ROOF FRAMING PLAN SHOWS PRECAST LINTEL |
| ABOVE DOOR OPENING.HOW CAN YOU HAVE A PRECAST LINTEL |
| ON A WOOD FRAMED WALL?. ALSO, FLOOR PLAN SHOW CONCRETE |
| BLOCK WALL AND CONCRETE FILLED COLUMNS AT BOTH ENDS OF |
| SWING DOOR. CLARIFY/REVISE DRAWINGS AS REQUIRED TO |
| MATCH. |
| |
| 2- WALL STEM WALL: |
| A) FIREBLOCKING AND FINISH CEILING INFORMATION IS |
| MIXED UP.THESE ARE TWO DIFFERENT CODE ISSUES. PROVIDE |
| INFORMATION FOR CEILING ASSEMBLY AND INFORMATION FOR |
| FIREBLOCKING SEPARATELY. REVISE/CLARIFY NOTE AS |
| REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| B) PROVIDE COMPLETE SPECS FOR SOFFIT INSTALLATION. |
| INFORMATION SUBMITTED IS INCOMPLETE."MASONRY TEXT. |
| FINISH SOFFITS W/3"CONT VENT" IS NOT ENOUGH |
| INFORMATION.SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| 3- STRUCTURAL LOADS INFORMATION IS INCORRECT: |
| A) FLOOR AND ROOF LIVE LOADS CAN'T BE ONLY 10PSF. |
| SEE SECTIONS R301 AND TABLE R301.5 OF 2004 FLORIDA |
| RESIDENTIAL CODE FOR REQUIRED LOADS TO BE CONSIDERED. |
| ALSO, INCLUDE ATTIC LIVE LOADS. |
| |
| 4- EMERGENCY EGRESS WINDOWS.2004 SEE FLORIDA |
| RESIDENTIAL BUILDING CODE AND 2006 REVISIONS AND CITE |
| SPECIFIC SECTIONS THAT APPLY TO THIS PROJECT. |
| INFORMATION SUBMITTED IS MISMATCHING THE FLORIDA |
| RESIDENTIAL CODE AND THE FLORIDA BUILDING CODE. |
| |
| 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) PRECAST LINTELS.NOA 03-0605.04 SUBMITTED IS FOR |
| 4", 6" AND 12" PRECAST LINTELS.NEED PRODUCT APPROVAL |
| FOR 8" PRECAST LINTELS. |
| |
| B) SINGLE HUNG WINDOWS. |
| |
| C) STORM SHUTTERS IF WINDOW DOESN'T HAVE IMPACT |
| GLASS. AND, CLEARLY SPECIFY ANCHOR TYPE AND SPACING TO |
| BE USED. SEE SHUTTERS ENGINEERING DRAWINGS. |
| |
| D) FLAT ROOF ASSEMBLY. AND CLEARLY IDENTIFY SPECIFIC |
| ASSEMBLY TO BE INSTALLED AND SPECIFIC FASTENING OPTION. |
| ALSO, PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER |
| AREAS PER RAS 117 AS IT'S TYPICALLY REQUIRED BY GENERAL |
| LIMITATION #7.SEE GENERAL LIMITATION #7 ON LAST PAGE |
| OF REPORT.SEE ATTACHED CITY POLICY FOR ROOFING |
| PERMITS. |
| |
| 6- ENGINEER OF RECORD TO REVIEWAND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| ***NOTE; MAKE SURE NAME OF ENGINEER WHO REVIEWS THE |
| PRODUCT APPROVAL IS CLEAR.PRODUCT APPROVALS SUBMITTED |
| ONLY STATES "REVIEW & APPROVED". NEED THE NAME OF |
| ENGINEER WHO REVIEWED THE PRODUCT APPROVAL. |
| |
| 7- PROVIDE THE ENERGY CALCULATIONS COMPLETELY FILLED |
| AND SIGNED AND DATED BY THE OWNER.AGENT.NOW AT TIME |
| OF PERMIT. NOTAT A LATER DATE. SEC. 13-600 FBC 2004. |
| |
| 8- OWES $44.06 FOR UPDATED VALUATION PLUSADDITIONAL |
| RESUBMITTAL FEES WILL BE CHARGED AFTER THE FIRST |
| RE-SUBMITTAL. |
| |
| |