Plan Review Notes
Plan Review Notes For Permit 07031080
Permit Number 07031080
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-26 10:18:53BUILDING REVIEW CHECKLIST:
 1-SHEET A1:
 A) ROOF FRAMING PLAN:
 * SPECIFIED SIMPSON CONNECTORS ARE WOOD TO WOOD
 CONNECTORS. NEED TO SPECIFY WOOD TO MASONRY CONNECTORS.
 SEE CURRENT CATALOG FOR CORRECT CONNECTOR AND FASTENING
 TYPE AND NUMBER AND REVISE AS REQUIRED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 ** CLEARLY SPECIFY CONNECTORS FOR ROOF RAFTER/JOIST TO
 MASONRY WALL AND FOR ROOF RAFTER TO ROOF JOIST. SEC.
 106.1.2 CITY AMENDEMNTS TO FBC 2004.
  
 B) FOUNDATION PLAN/FLOOR PLAN: STARTER COLUMN IS NOT
 DRAWN CORRECTLY. NOTE CALLS FOR CONCRETE POURED COLUMN,
 WHILE DRAWING SHOW CONCRETE FILLED CELL. REVISE AS
 REQUIRED TO MATCH AND AVOID CONFUSIONS.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 2- SHEET A2:
 A) WALL STEM DETAIL:
 * REVISE SIMPSON CONNECTORS. SEE ITEM 1(A) ABOVE.
 ** REVISETYPE OF FLAT ROOF SPECIFIED. SEE PRODUCT
 APPROVAL FOR SPECIFIC MANUFACTURER AND ASSEMBLY TO BE
 INSTALLED.WHAT DOES BY "BITUMEN" ON 43 LB STANDS
 FOR?. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 *** REVISE FASCIA DETAIL.REVISE SIZE AND PROPER WAY
 OF INSTALLING DRIP EDGE. SEC. 106.1.2 CITY AMENDEMNTS
 TO FBC 2004.
 **** SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.8 OF
 2004 FLORIDA RESIDENTIAL CODE.
 ***** THERE ARE 2 DIFFERENT SPECS FOR FURRING STRIPS ON
 THE SAME WALL. REVISE AS REQUIRED.
  
 B) SHOWER RECESS DETAIL DOESN'T MATCH INFORMATION ON
 FOUNDATION PLAN. REVISE AS REQUIRED.
  
 C) PROVIDE ONLY THE INFORMATION THAT CORRESPONDS TO
 THIS PROJECT TO EXPEDITE REVIEW PROCESS AND AVOID
 CONFLICTS/CONFUSIONS. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 D) REVISE DESIGN WIND PRESSURES FOR ROOF AREA. NEED
 TO USE 10SFTRIBUTARY AREA FOR COMPONENTS AND CLADDING
 FOR ROOF ASSEMBLY.SEE REVISED TABLE 1609.6.2.1(2) OF
 FBC 2004.
  
 3-ENGINEER NEEDS TO CONTACT DBPR TO RESOLVE ISSUE
 WITH HIS LICENSE STATUS.NEED CURRENT AND ACTIVE
 STATUS TO PROVIDE ENGINEERING SERVICES. DBPR WEBSITE
 SHOWS LICENSE UNDER A DELINQUENT STATUS.NEED TO
 CORRECT THIS BEFORE RE-SUBMITTING PLANS.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS.
 B) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- NEED TO PROVIDE THE ENERGY CALCULATIONS COMPLETELY
 FILLED AND SIGNED AND DATEDAS REQUIRED BY SEC. 13-600
 FBC 2004.
  
 7- ENGINEER SEAL IS NOT LEGIBLE AND WHAT'S DATED
 1-30-06?
  
 8- OWES $44.06 FOR UPDATED VALUATION AND RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712