Plan Review Notes For Permit 07031030 |
Permit Number |
07031030 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-01-22 12:49:11 | REDLINED 700.12F AS THE EM LIGHTS ARE NOW SHOWN AS | | EXISTING YET THE FIXTURES SHALL BE VERIFIED TO BE | | CIRCUITED PER 700.12F. THIS REQUIRES THESE FIXTURES TO | | BE CIRCUITED TO THE LOCAL LIGHTING BRNACH CIRCUIT. |
|