2007-03-31 18:19:32 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SEE NOTES ON PLANS WHICH STATE THE 2001 FBC. |
| |
| 2) NOTE: PLEASE KNOW IF THE ARCHITECT OF RECORD IS |
| EMPLOYED BY THE CONTRACTOR THEN THE CONSTRUCTION |
| COMPANY IS PROVIDING ARCHITECTURAL SERVICES AND MUST |
| CONTAIN A CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE |
| CONTACT MR. DAVID MINACCI, STATES LEGAL COUNSEL TO THE |
| BOARD OF ARCHITECTS. |
| MUST OBTAIN THE CA/FIRM LICENSE NUMBER. |
| FS 481.219, AND PLACE ON TITLE BLOCKS PER FAC |
| 61G1-16.004. |
| ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE. |
| ** THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS |
| MADE BY ANY OTHER TRADES. ANY STAMPED SHEETS ARE NOW |
| VOID. |
| |
| 3) NOTE: PLEASE PROVIDE MORE ELECTRICAL DETAIL ON |
| PLANS. PLEASE INCLUDE ALL ELECTRICAL DEVICES FOR |
| RECEPTACLES AND LIGHTING. NEW OR EXISTING? |
| PLEASE PROVIDE LIGHTING DETAILS IF NEW, PLEASE INDICATE |
| IF THERE IS A NEW OR EXISTING EMERGENCY LIGHT FIXTURE? |
| PLEASE SEE 700.12E FOR CIRCUITING IF NEW. |
| PLEASE SEE NFPA-101 7.8, 7.9 |
| |
| 4) NOTE: PLEASE PROVIDE CIRCUITING FOR NEW ELECTRICAL |
| OR ARE THESE LOADS ON EXISTING CIRCUITS? |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE PROVIDE TIMES AND TYPES OF DEVICES FOR |
| NEW OC SENSORS. PLEASE BE AWARE OF DEVICE IN ORDER TO |
| PROPERLY PROVIDE COVERAGE FOR ALL AREAS. THIS MAY BE |
| REQUIRED TO BE A COMBINATION DEVICE. |
| PLEASE SEE MAXIMUM TIMES IN 13-415.1.ABC.1.1, .1.2. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |