Plan Review Notes
Plan Review Notes For Permit 07031029
Permit Number 07031029
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-31 18:25:10** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE NOTES ON PLANS WHICH STATE THE 2001 FBC.
  
 2) NOTE: PLEASE KNOW IF THE ARCHITECT OF RECORD IS
 EMPLOYED BY THE CONTRACTOR THEN THE CONSTRUCTION
 COMPANY IS PROVIDING ARCHITECTURAL SERVICES AND MUST
 CONTAIN A CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE
 CONTACT MR. DAVID MINACCI, STATES LEGAL COUNSEL TO THE
 BOARD OF ARCHITECTS.
 MUST OBTAIN THE CA/FIRM LICENSE NUMBER.
 FS 481.219, AND PLACE ON TITLE BLOCKS PER FAC
 61G1-16.004.
 ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE.
 ** THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER TRADES. ANY STAMPED SHEETS ARE NOW
 VOID.
  
 3) NOTE: PLEASE PROVIDE MORE ELECTRICAL DETAIL ON
 PLANS. PLEASE INCLUDE ALL ELECTRICAL DEVICES FOR
 RECEPTACLES AND LIGHTING. NEW OR EXISTING?
 PLEASE PROVIDE LIGHTING DETAILS IF NEW, PLEASE INDICATE
 IF THERE IS A NEW OR EXISTING EMERGENCY LIGHT FIXTURE?
 PLEASE SEE 700.12E FOR CIRCUITING IF NEW.
 PLEASE SEE NFPA-101 7.8, 7.9
  
 4) NOTE: PLEASE PROVIDE CIRCUITING FOR NEW ELECTRICAL
 OR ARE THESE LOADS ON EXISTING CIRCUITS?
 FBC 106.1.2
  
 5) NOTE: PLEASE PROVIDE TIMES AND TYPES OF DEVICES FOR
 NEW OC SENSORS. PLEASE BE AWARE OF DEVICE IN ORDER TO
 PROPERLY PROVIDE COVERAGE FOR ALL AREAS. THIS MAY BE
 REQUIRED TO BE A COMBINATION DEVICE.
 PLEASE SEE MAXIMUM TIMES IN 13-415.1.ABC.1.1, .1.2.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]