Date |
Text |
2007-04-07 10:41:01 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS LIST, SAME PAPERWORK SUBMITTED. |
| |
| 1.)CONNECTION C4 REQUIRES 6" SPACING; YOUR |
| INSTALLATION SCHEDULE SPECIFIES 10". |
| |
| NOTE THAT YOUR "GENERIC" INSTALLATION SCHEDULE DOES NOT |
| REFER TO A CONNECTION TYPE.IF THE CONNECTION |
| SPECIFIED IS NOT COMPLIANT FOR ALL CONNECTION TYPES, OR |
| YOU ARE USING DIFFERENT CONNECTION TYPES FOR DIFFERENT |
| OPENINGS, THIS SCHEDULE IS NOT USEFUL AS IT IS TO |
| DETERMINE CODE COMPLIANCE AND TO ASSIST IN INSPECTIONS. |
| PERMITS WILL BE ISSUED FROM THE "GENERIC" INSTALLATION |
| SCHEDULE IF IT IS CLEARLY CODE COMPLIANT.IF IT |
| REQUIRES THE INSPECTOR TO READ THROUGH THE PRODUCT |
| APPROVAL AND CODE COMPLIANCE IS NOT EASILY DETERMINED, |
| A SCHEDULE REFERRING TO EACH OPENING WILL BE REQUIRED |
| AS STATED IN THE BUILDING OFFICIAL'S WRITTEN POLICY, |
| SEE ATTACHED. |
| |
| ALSO NOTE THAT AS THIS IS A WRITTEN POLICY FROM THE |
| BUILDING OFFICIAL, IF I ISSUE A PERMIT USING MY BEST |
| JUDGEMENT THE I HAVE ENOUGH INFORMATION TO DETERMINE |
| CODE COMPLIANCE BASED ON THE "GENERIC" INSTALLATION |
| SCHEDULE, THIS WILL BE ON A CASE BY CASE BASIS AND |
| OTHER PLANS EXAMINERS IN THIS DEPARTMENT MIGHT NOT |
| ISSUE WITH THE SAME INFORMATION. |
| |
| NOTE THAT ALL OTHER CONTRACTORS ARE REQUIRED TO PROVIDE |
| ALL REQUIRED INFORMATION. |
| |