2007-04-07 10:41:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST, SAME PAPERWORK SUBMITTED.
  
 1.)CONNECTION C4 REQUIRES 6" SPACING; YOUR
 INSTALLATION SCHEDULE SPECIFIES 10".
  
 NOTE THAT YOUR "GENERIC" INSTALLATION SCHEDULE DOES NOT
 REFER TO A CONNECTION TYPE.IF THE CONNECTION
 SPECIFIED IS NOT COMPLIANT FOR ALL CONNECTION TYPES, OR
 YOU ARE USING DIFFERENT CONNECTION TYPES FOR DIFFERENT
 OPENINGS, THIS SCHEDULE IS NOT USEFUL AS IT IS TO
 DETERMINE CODE COMPLIANCE AND TO ASSIST IN INSPECTIONS.
 PERMITS WILL BE ISSUED FROM THE "GENERIC" INSTALLATION
 SCHEDULE IF IT IS CLEARLY CODE COMPLIANT.IF IT
 REQUIRES THE INSPECTOR TO READ THROUGH THE PRODUCT
 APPROVAL AND CODE COMPLIANCE IS NOT EASILY DETERMINED,
 A SCHEDULE REFERRING TO EACH OPENING WILL BE REQUIRED
 AS STATED IN THE BUILDING OFFICIAL'S WRITTEN POLICY,
 SEE ATTACHED.
  
 ALSO NOTE THAT AS THIS IS A WRITTEN POLICY FROM THE
 BUILDING OFFICIAL, IF I ISSUE A PERMIT USING MY BEST
 JUDGEMENT THE I HAVE ENOUGH INFORMATION TO DETERMINE
 CODE COMPLIANCE BASED ON THE "GENERIC" INSTALLATION
 SCHEDULE, THIS WILL BE ON A CASE BY CASE BASIS AND
 OTHER PLANS EXAMINERS IN THIS DEPARTMENT MIGHT NOT
 ISSUE WITH THE SAME INFORMATION.
  
 NOTE THAT ALL OTHER CONTRACTORS ARE REQUIRED TO PROVIDE
 ALL REQUIRED INFORMATION.
  