Date |
Text |
2007-04-10 09:53:27 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| |
| COMMENTS FROM FIRST REVIEW, NOT PROPERLY ADDRESSED: |
| |
| |
| _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| THIS WAS ADDRESSED BUT ONLY ONE SET WAS SUBMITTED.TWO |
| COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR |
| PERMITTING, FBC*106.1. |
| |
| _XX_4.)1ST REVIEW - FOR THE FLAT DECK, SELECT THE |
| APPROVED ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH |
| FASTENER YOU ARE USING IF THE OPTIONS HAVE DIFFERENT |
| PRESSURE LIMITATIONS. NOTE THAT THE ASSEMBLY YOU CHOSE |
| IS LIMITED TO -45PSF, NO ENHANCED FASTENING ALLOWED, |
| GENERAL LIMITATION #9. |
| |
| 2ND REVIEW - TWO DIFFERENT ASSEMBLIES ARE MARKED, ONE |
| WITH GENERAL LIMITATION #9.THE ENGINEER SPECIFIES THE |
| OTHER ASSEMBLY.DO NOT MARK MORE THAN ONE ASSEMBLY. |
| |
| _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES. |
| |
| 2ND REVIEW - THIS WAS DONE WITH ENGINEERING.HOWEVER, |
| THE ENGINEER STATES THIS IS A RECOVER DECK, BUT YOUR |
| APPLICATION STATES THAT THIS IS A REROOF. |
| |
| _XX_ 7.)PRODUCT APPROVAL IS FOR RECOVER DECK, |
| APPLICATION IS FOR REROOF. |
| |
| 2ND REVIEW - APPLICATION IS NOT CONSISTENT WITH |
| ENGINEERING AND PRODUCT APPROVAL SUBMITTED.PLEASE |
| ADDRESS. |
| |
| |
| |
| |
| |
| |
| |