Plan Review Notes
Plan Review Notes For Permit 07031022
Permit Number 07031022
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-10 09:53:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 COMMENTS FROM FIRST REVIEW, NOT PROPERLY ADDRESSED:
  
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 THIS WAS ADDRESSED BUT ONLY ONE SET WAS SUBMITTED.TWO
 COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR
 PERMITTING, FBC*106.1.
  
 _XX_4.)1ST REVIEW - FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH
 FASTENER YOU ARE USING IF THE OPTIONS HAVE DIFFERENT
 PRESSURE LIMITATIONS. NOTE THAT THE ASSEMBLY YOU CHOSE
 IS LIMITED TO -45PSF, NO ENHANCED FASTENING ALLOWED,
 GENERAL LIMITATION #9.
  
 2ND REVIEW - TWO DIFFERENT ASSEMBLIES ARE MARKED, ONE
 WITH GENERAL LIMITATION #9.THE ENGINEER SPECIFIES THE
 OTHER ASSEMBLY.DO NOT MARK MORE THAN ONE ASSEMBLY.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 2ND REVIEW - THIS WAS DONE WITH ENGINEERING.HOWEVER,
 THE ENGINEER STATES THIS IS A RECOVER DECK, BUT YOUR
 APPLICATION STATES THAT THIS IS A REROOF.
  
 _XX_ 7.)PRODUCT APPROVAL IS FOR RECOVER DECK,
 APPLICATION IS FOR REROOF.
  
 2ND REVIEW - APPLICATION IS NOT CONSISTENT WITH
 ENGINEERING AND PRODUCT APPROVAL SUBMITTED.PLEASE
 ADDRESS.
  
  
  
  
  
  
  