Plan Review Notes
Plan Review Notes For Permit 07031012
Permit Number 07031012
Review Stop M
Sequence Number 4
Notes
Date Text
2007-12-07 11:16:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ***REVISION DENIED ***
 1) CHANGES MAY NOT BE DONE BY HAND TO ENGINEER SEALED
 PLANS.
  
 2) THE CHANGES TO THE PLANS BY HAND DO NOT ADDRESS THE
 COMMENTS FROM THE LAST REVIEW 12-3-07 AND MAKE NO
 SENSE. PLEASE SEE NOTES FROM LAST REVIEW AND MAKE
 CORRECTIONS.
  
 ** NOTES FROM LAST REVIEW 12-3-07 **
 1) EXHAUST HOOD #1 HAS TWO 9"X16" EXHAUST DUCTS THE
 EXHAUST FAN IS 2,500 CFM'S , THAT WOULD PUT THE EXHAUST
 DUCT VELOCITY AT 1,250 CFM'S. SEE NOTE #4 ON PAGE 2 OF
 THE PLANS AND SEE 2004 FBC/M 506.3.4 STATES DUCT
 VELOCITY NOT LESS THAN 1,500 CFM'S. PLEASE CORRECT.
  
 2) PAGE 1 OF PLANS FRONT ELEVATION OF HOOD #1 SHOWS THE
 EXHAUST FAN AND CURB NOT TO BE SECURED TO THE ROOF,
 PLEASE COMPLY WITH 2004 FBC 1609.
  
 3) NEED TO ADD A FRONT VIEW FOR HOOD #2 TO THE PLANS.
  
 4) PAGE 1 SECTION VIEW FOR HOOD #1 IS LISTING THE
 SUPPLY AND EXHAUST FANS AS #1, PLEASE CORRECT.
  
 5) PLEASE LABEL HOODS AS #1 AND #2 ON PLAN.
  
 6) PAGE TWO HOOD SCHEDULE SHOWS HOOD 1 EXHAUST SIZE AS
 20X12, PLEASE CORRECT TO (2) 9X16.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]