2007-12-07 11:16:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| ***REVISION DENIED *** |
| 1) CHANGES MAY NOT BE DONE BY HAND TO ENGINEER SEALED |
| PLANS. |
| |
| 2) THE CHANGES TO THE PLANS BY HAND DO NOT ADDRESS THE |
| COMMENTS FROM THE LAST REVIEW 12-3-07 AND MAKE NO |
| SENSE. PLEASE SEE NOTES FROM LAST REVIEW AND MAKE |
| CORRECTIONS. |
| |
| ** NOTES FROM LAST REVIEW 12-3-07 ** |
| 1) EXHAUST HOOD #1 HAS TWO 9"X16" EXHAUST DUCTS THE |
| EXHAUST FAN IS 2,500 CFM'S , THAT WOULD PUT THE EXHAUST |
| DUCT VELOCITY AT 1,250 CFM'S. SEE NOTE #4 ON PAGE 2 OF |
| THE PLANS AND SEE 2004 FBC/M 506.3.4 STATES DUCT |
| VELOCITY NOT LESS THAN 1,500 CFM'S. PLEASE CORRECT. |
| |
| 2) PAGE 1 OF PLANS FRONT ELEVATION OF HOOD #1 SHOWS THE |
| EXHAUST FAN AND CURB NOT TO BE SECURED TO THE ROOF, |
| PLEASE COMPLY WITH 2004 FBC 1609. |
| |
| 3) NEED TO ADD A FRONT VIEW FOR HOOD #2 TO THE PLANS. |
| |
| 4) PAGE 1 SECTION VIEW FOR HOOD #1 IS LISTING THE |
| SUPPLY AND EXHAUST FANS AS #1, PLEASE CORRECT. |
| |
| 5) PLEASE LABEL HOODS AS #1 AND #2 ON PLAN. |
| |
| 6) PAGE TWO HOOD SCHEDULE SHOWS HOOD 1 EXHAUST SIZE AS |
| 20X12, PLEASE CORRECT TO (2) 9X16. |
| |