Plan Review Notes For Permit 07031012 |
Permit Number |
07031012 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-12-03 09:09:32 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | ***REVISION DENIED *** | | 1) EXHAUST HOOD #1 HAS TWO 9"X16" EXHAUST DUCTS THE | | EXHAUST FAN IS 2,500 CFM'S , THAT WOULD PUT THE EXHAUST | | DUCT VELOCITY AT 1,250 CFM'S. SEE NOTE #4 ON PAGE 2 OF | | THE PLANS AND SEE 2004 FBC/M 506.3.4 STATES DUCT | | VELOCITY NOT LESS THAN 1,500 CFM'S. PLEASE CORRECT. | | | | 2) PAGE 1 OF PLANS FRONT ELEVATION OF HOOD #1 SHOWS THE | | EXHAUST FAN AND CURB NOT TO BE SECURED TO THE ROOF, | | PLEASE COMPLY WITH 2004 FBC 1609. | | | | 3) NEED TO ADD A FRONT VIEW FOR HOOD #2 TO THE PLANS. | | | | 4) PAGE 1 SECTION VIEW FOR HOOD #1 IS LISTING THE | | SUPPLY AND EXHAUST FANS AS #1, PLEASE CORRECT. | | | | 5) PLEASE LABEL HOODS AS #1 AND #2 ON PLAN. | | | | 6) PAGE TWO HOOD SCHEDULE SHOWS HOOD 1 EXHAUST SIZE AS | | 20X12, PLEASE CORRECT TO (2) 9X16. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|