2007-12-28 14:54:07 | REVISION DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| |
| 1. SHT P-1 REVISION DENIED. MOST CLOUDED REVISIONS SHOW |
| NO CHANGE.--THERE ARE CLEANOUTS REQUIRED AS THE |
| PIPING FOR THE SANITARY EXITS THE BUILDING NEAR THE |
| JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER |
| AND AS THE PIPING FOR THE GREASE INTERCEPTOR EXITS THE |
| INTERCEPTOR. THESE ARE SHOWN TO HAVE BEEN DELETED. |
| THESE SHOULD BE SHOWN ON THE PLAIN VIEW ALSO.-- |
| TOTAL BTU'S AT THE TOTAL GAS CONNECTED LOAD HAS BEEN |
| CHANGED FROM 978,000 TO 898,000 TOTAL BTU'S. THE |
| ORIGINAL TOTAL WAS CORRECT. THE NEW TOTAL IS DENIED. |
| --THE TABLE FOR THE GAS WAS CHANGED FROM 402.4(2) TO |
| 402.4(1). THIS IS NOT APPROVED. THE ORIGINAL TABLE IS |
| CORRECT.--THE NOTE INDICATING THE DISTANCE FROM THE |
| POINT OF DELIVERY ETC. ENDS WITH A GAS SIZING TABLE OF |
| A.3.1(4). THIS TABLE DOES NOT EXIST IN THE 2004 FUEL |
| GAS CODE AND IS NOT CORRECT. THE CORRECT TABLE IS |
| 402.4(1). PLEASE CHANGE NOTE. PLEASE SUBMIT REVISIONS |
| THAT CHANGE FROM THE ORIGINAL STAMPED/REVIEWED PLANS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |