2007-12-07 15:19:57 | REVISION DENITED; | | 1. MAKE ALL PLUMBING REVISIONS ON "P" PAGES. | | 2. FLAT PIPING ON PAGE A-2 DOES NOT MATCH SANITARY | | RISER DIAGRAM ON P-1. | | 3. PLANS SHOW A 750 GAL. GREASE TRAP OUTSIDE WITH THE | | ROTISARY, 3-COMPARTMENT SINK AND MOP SINKALL DRAINING | | INTO A GREASE LINE. | | 4. THE GREASE TRAP WAS SIZED BY THE UTILITY DEPARTMENT. | | TO CHANGE THE SIZE AND TYPE OF TRAP YOU MUST GET | | APPROVAL FROM UTILITIES BEFORE SUBMITING REVISION TO | | THE BUILDING DEPARTMENT. | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 805-6695 |
|