Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop P
Sequence Number 3
Notes
Date Text
2007-08-31 07:36:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
  
 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE
 SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP.
 ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY
 WPB.
 ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE
 NOT BEEN ATTACHED TO EACH SET OF PLAN.
 ******NO RESPONSE. STAMPED/REVIEWED SHEETS FROM DBPR
 HAVE BEEN DELETED FROM EACH SET. THESE ARE REQUIRED AS
 WELL AS THE TWO PAGE "SPECIFICATION WORKSHEETS". THE
 WORKSHEETS SHALL BE ATTACHED TO THE SHEETS STAMPED &
 REVIEWED BY DBPR AND ONE SHEET SHALL BE INSERTED INTO
 EACH SET OF PLANS AS REQUIRED BY SECTION 102.2.1.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT
 RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN
 WILLIAMS (561) 822-2284, [email protected]. THEIR FAX
 NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124.
 --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE,
 MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE
 ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).--
 THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE
 FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING
 VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III
 SECTION 9--124(7)(B).
 ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL
 COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN
 APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO
 OR MR. WILLIAMS.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 5. OK
  
 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A
 FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE
 FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE
 OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE
 SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT
 GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO
 BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A
 RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE - ******NO RESPONSE,
 COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO
 VERIFY COMPLIANCE.
 B. 11-4.16.5 FLUSH CONTROLS - ******NO RESPONSE,
 COMMENT NOT ADDRESSED.
 ___FOR LAV
 A. 11-4.19.3 CLEAR FLOOR SPACE - ******NO RESPONSE,
 COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO
 VERIFY COMPLIANCE.
 B. 11-4.19.4 EXPOSED PIPES & SURFACES - ******NO
 RESPONSE, COMMENT NOT ADDRESSED.
 C. 11-4.19.5 FAUCETS - ******NO RESPONSE, COMMENT NOT
 ADDRESSED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
 ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT
 SHOWN.
 ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON
 THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT
 APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3.
 - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS
 APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF
 VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH
 APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2).
  
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN.
 ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO
 111FT, NOT 105 AS SHOWN.
  
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS.
 ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND
 COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED.
 ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS
 INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED
 WITH MODEL NUMBER INDICATED.
  
 F. N/A
 F. N/A
 G. OK
  
 ************NEW COMMENTS************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE
 GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE
 GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR
 PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE
 INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING
 CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489.
 ******NO RESPONSE. PLEASE INDICATE PLUMBING CONTRACTOR
 RESPONSIBILITY FOR THESE INSTALLATIONS.
  
 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A
 NOTICE AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION. ******SUBMIT ONE SET
 OF VOID SHEETS FOR COMPARISON WHEN RESUBMITTING
 PLANS.******
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved