Date |
Text |
2007-08-31 07:36:31 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| CITY WPB MUNICIPAL CODE |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| ******FROM PREVIOUS REVIEWS: |
| |
| 1. OK |
| 2. OK |
| |
| 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS |
| REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE |
| SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP. |
| ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO |
| EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY |
| WPB. |
| ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE |
| NOT BEEN ATTACHED TO EACH SET OF PLAN. |
| ******NO RESPONSE. STAMPED/REVIEWED SHEETS FROM DBPR |
| HAVE BEEN DELETED FROM EACH SET. THESE ARE REQUIRED AS |
| WELL AS THE TWO PAGE "SPECIFICATION WORKSHEETS". THE |
| WORKSHEETS SHALL BE ATTACHED TO THE SHEETS STAMPED & |
| REVIEWED BY DBPR AND ONE SHEET SHALL BE INSERTED INTO |
| EACH SET OF PLANS AS REQUIRED BY SECTION 102.2.1. |
| |
| 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY |
| THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT |
| RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN |
| WILLIAMS (561) 822-2284, [email protected]. THEIR FAX |
| NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124. |
| --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE, |
| MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE |
| ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).-- |
| THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE |
| FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING |
| VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III |
| SECTION 9--124(7)(B). |
| ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL |
| COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN |
| APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO |
| OR MR. WILLIAMS. |
| ******NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 5. OK |
| |
| 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A |
| FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE |
| FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE |
| OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE |
| SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT |
| GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO |
| BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A |
| RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK. |
| ******NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 7. OK |
| 8. OK |
| 9. OK |
| 10. OK |
| 11. OK |
| 12. OK |
| 13. OK |
| |
| 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW |
| COMPLIANCE WITH THE FOLLOWING: |
| ___FOR W/C |
| A. 11-4.16.2 CLEAR FLOOR SPACE - ******NO RESPONSE, |
| COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO |
| VERIFY COMPLIANCE. |
| B. 11-4.16.5 FLUSH CONTROLS - ******NO RESPONSE, |
| COMMENT NOT ADDRESSED. |
| ___FOR LAV |
| A. 11-4.19.3 CLEAR FLOOR SPACE - ******NO RESPONSE, |
| COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO |
| VERIFY COMPLIANCE. |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES - ******NO |
| RESPONSE, COMMENT NOT ADDRESSED. |
| C. 11-4.19.5 FAUCETS - ******NO RESPONSE, COMMENT NOT |
| ADDRESSED. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| |
| 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED |
| LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL |
| AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & |
| 409.5. |
| ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT |
| SHOWN. |
| ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON |
| THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT |
| APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3. |
| - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS |
| APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF |
| VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH |
| APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2). |
| |
| |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. |
| ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO |
| 111FT, NOT 105 AS SHOWN. |
| |
| C. OK |
| D. OK |
| |
| E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS. |
| ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND |
| COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED. |
| ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS |
| INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED |
| WITH MODEL NUMBER INDICATED. |
| |
| F. N/A |
| F. N/A |
| G. OK |
| |
| ************NEW COMMENTS************ |
| |
| 1B. OK |
| 2B. OK |
| 3B. OK |
| 4B. OK |
| 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE |
| GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE |
| GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR |
| PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE |
| INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING |
| CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489. |
| ******NO RESPONSE. PLEASE INDICATE PLUMBING CONTRACTOR |
| RESPONSIBILITY FOR THESE INSTALLATIONS. |
| |
| 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A |
| NOTICE AT THIS TIME. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. ******SUBMIT ONE SET |
| OF VOID SHEETS FOR COMPARISON WHEN RESUBMITTING |
| PLANS.****** |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |
| |
| |
| . |