Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop G
Sequence Number 3
Notes
Date Text
2007-08-31 07:38:53DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
 ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT
 SHOWN.
 ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON
 THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT
 APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3.
 - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS
 APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF
 VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH
 APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2).
  
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN.
 ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO
 111FT, NOT 105FT AS SHOWN.
  
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS.
 ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND
 COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED.
 ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS
 INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED
 WITH MODEL NUMBER INDICATED. PLEASE CLARIFY.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .