Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop P
Sequence Number 2
Notes
Date Text
2007-07-10 11:47:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING
 APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S
 DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE
 APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2.
 PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO
 REFLECT THE CORRECT ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT BEEN
 CHANGED ON THE ARCHITECTURAL SHEETS.
  
 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE
 ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE
 BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE
 SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP.
 ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY
 WPB.
 ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE
 NOT BEEN ATTACHED TO EACH SET OF PLAN.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT
 RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN
 WILLIAMS (561) 822-2284, [email protected]. THEIR FAX
 NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124.
 --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE,
 MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE
 ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).--
 THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE
 FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING
 VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III
 SECTION 9--124(7)(B).
 ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL
 COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN
 APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO
 OR MR. WILLIAMS.
  
 5. OK
  
 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A
 FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE
 FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE
 OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE
 SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT
 GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO
 BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A
 RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK.
  
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS,
 (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT
 IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER
 TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV
 BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO
 BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION
 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9.
 ****RESPONSE NOTED, BUT A FULL OPEN VALVE IS REQUIRED
 ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE
 INTO THE STRUCTURE. SECTION 606.1(2).
  
 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE METHOD. ****RESPONSE
 NOTED, BUT A CHECK VALVE DOES NOT CONTROL THERMAL
 EXPANSION.PLEASE INDICATE PROPER APPROVED METHOD OF
 CONTROLING THERMAL EXPANSION.
  
 13. OK
  
 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAV
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO
 BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR
 FLOOR SPACE REQUIRED FOR THE LAV).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
 ******RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT
 SHOWN.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ******RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN.
  
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESS.
  
 F. N/A
 F. N/A
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW
 VALVES & UNION ON RISER DIAGRAM. (SEE COMMENT #1).
  
 ************NEW COMMENTS************
  
 1B. (NEW) SHT P-1 INDICATES A WATER FILTER. THE WATER
 FILTER SHALL MEET THE REQUIREMENTS OF NSF 42. SUBMIT
 MANUF. SPECIFICATIONS SHOWING COMPLIANCE. SECTION
 611.1.
  
 2B. SHT P-1 A VENT IS REQUIRED ON THE GREASE SYSTEM.
 SECTION 901.2.
  
 3B. SHT P-1 A SERVICE SINK IS REQUIRED PER TABLE 403.1.
 SINK SHALL BE CONNECTED TO THE GREASE SYSTEM. INDICATE
 THE LOCATION ON THE FLOOR PLAN, GREASE RISER DIAGRAM
 AND THE WATER RISER DIAGRAM.
  
 4B. SHT M-1 GAS WATER HEATER DETAIL. A FLOOR DRAIN IS
 NOT AN APPROVED INDIRECT WASTE RECEPTOR. A FLOOR SINK
 OR HUB DRAIN SHALL BE USED. SECTIONS 802.3 & 802.3.2.
  
 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE
 GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE
 GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR
 PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE
 INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING
 CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489.
  
 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A
 NOTICE AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved