2007-07-10 11:29:40 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| ******FROM PREVIOUS REVIEW: |
| |
| 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED |
| LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL |
| AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & |
| 409.5. |
| ******RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT |
| SHOWN. |
| |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ******RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. |
| |
| C. OK |
| D. OK |
| |
| E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ******RESPONSE NOTED, BUT COMMENT NOT ADDRESS. |
| |
| F. N/A |
| F. N/A |
| |
| G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW |
| VALVES & UNION ON RISER DIAGRAM. (SEE COMMENT #1). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |