Date |
Text |
2007-06-22 09:03:45 | *** UNSAT 2ND REVIEW *** |
| |
| *** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW HAVE NOT |
| BEEN ADDRESSED AND THERE ARE SOME NEW COMMENTS DUE TO |
| CHANGES IN PLANS. PLEASE SEE THAT MOST OF THE ITEMS ARE |
| FROM PREVIOUS REVIEW. |
| |
| ** ONCE AGAIN, DUE TO THE AMOUNT OF COMMENTS AND |
| UN-LICENSED INFORMATION, ONE SET OF PLANS ARE BEING |
| RETAINED BY THIS OFFICE. |
| |
| 1) NOTE:PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL |
| FIRM. AS STATED ON PREVIOUS REVIEW NOT CERTIFICATE OF |
| AUTHORIZATION NUMBER IS ON PLANS AND NOT INFORMATION ON |
| THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION |
| FROM THE STATE COULD BE LOCATED. PLANS ARE BEING |
| RETAINED AND INFORMATION TO THE STATE BOARD OF |
| ARCHITECTS AND STATE LEGAL COUNSEL TO THE BOARD WILL BE |
| NOTIFIED. |
| PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING THE |
| REQUIRED LICENSURE PER FS 481.219 AND FAC 61G1-16.004. |
| PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER |
| OR NOT COMMENT IS MADE BY OTHER REVIEWERS. |
| |
| 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES, |
| PANEL SCHEDULE AND PLANS. |
| PLEASE SEE THE ELECTRICAL RISER IS STILL SHOWING A NEW |
| SERVICE WHICH IS NOT PERMITTED AND IS NOT GRANTED BY |
| THIS OFFICE. PLEASE SEE THE PREVIOUS NOTES ON PLANS HAD |
| SOME DIFFERENCES IN THE SIZE OF SERVICE AND NOW THEY |
| HAVE BEEN CHANGED BUT HOWEVER ARE STILL NOT CORRECT. |
| PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A |
| 300A PANEL IN ONE NOTE, 200AMP IN ANOTHER NOTE. |
| THIS LOCATION HAS BEEN LOOKED AT BY THIS OFFICE AND THE |
| TENANT SPACE DOES NOT FALL UNDER THE DEFINITION OF A |
| *BUILDING*. PLEASE SEE THAT COMPLETE INFORMATION FOR |
| THE ENTIRE BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS |
| TO BE A TENANT SPACE WHICH IS PART OF A LARGER |
| BUILDING. PLEASE KNOW THAT ADDITIONAL SERVICE IS NOT |
| BEING GRANTED AS IT DOES NOT MEET 230.2. THERE IS NO |
| INDICATION ON PLANS WHICH SHOWS COMPLIANCE WITH THE FBC |
| TO CONSIDER THIS A *SEPARATE BUILDING BY DEFINITION*. |
| PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING |
| WILL NEED TO UP-GRADED IF THE EXISTING SERVICE IS NOT |
| OF SUFFICIENT SIZE. |
| ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING |
| SERVICE OR NEW. AS THE SERVICE AS PERMITTED HAS NOT |
| BEEN SHOWN A REVIEW OF SERVICE CAN NOT BE DONE AT THIS |
| TIME. |
| |
| 3) NOTE: PLEASE SEE THE PREVIOUS NOTES REQUESTED A |
| COMPLETED RISER HOWEVER SOME OF THE INFORMATION IS |
| STILL NOT ON PLANS. PLEASE SEE THE GROUNDING ELECTRODE |
| SYSTEM AS REQUIRED PER 250.50 IS NOW SHOWING THE |
| BUILDING/FOOTER STEEL? THIS IS AN EXISTING BUILDING AND |
| THE EXISTING FOOTER STEEL IS NOT REQUIRED TO BE |
| UNCOVERED IF THE ATTACHMENT IS NOT ALREADY MADE. THIS |
| WOULD INDEED AFFECT THE STRUCTURAL INTEGRITY OF THE |
| EXISTING FOOTER |
| PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE |
| EQUIPMENT. |
| PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70 |
| |
| 4) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH |
| THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13 AS |
| PREVIOUSLY REQUESTED. PLEASE SEE 13-413.1ABC.1, |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE |
| 13-415.1.AB.1.1, 13-415.2. |
| PLEASE SEE A LIGHTING CONTROL PANEL IS NOW NOTED BUT |
| THE NO INFORMATION WAS SHOWN FOR THE LIGHTING CONTROL |
| PANEL OR SYSTEM. |
| PLEASE SEE NOT TIMED SCHEDULING WAS SUBMITTED. |
| PLEASE SEE NO TIMES WERE INDICATED FOR OVER RIDES. |
| PLEASE SEE NO SPECIFIC TYPES OF DEVICES ARE INDICATED. |
| PLEASE SEE ALL LOCATIONS FOR OVER RIDES ARE NOT SHOWN |
| AS REQUIRED PER SECTIONS ABOVE. |
| PLEASE SEE NOT ALL SEPARATE SPACES ARE SHOWING REQUIRED |
| DEVICES. |
| PLEASE SEE THE LIGHTING POWER DENSITIES ARE NOT |
| CORRECT. |
| PLEASE SEE TRACK LIGHTING PER 13-415.2.ABC.1.2 WAS NOT |
| SHOWN OR CORRECT. |
| PLEASE SEE13-415.2.ABC.1.2 (3, 4) |
| NO FIXTURE LEGEND WAS SUBMITTED WHICH INDICATES THE |
| FIXTURES AS NOTED ON PLANS, NO WATTAGE ON FIXTURES ETC |
| NO ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS, ETC |
| AS THERE IS MUCH INFORMATION FOR CHAPTER 13 WHICH WAS |
| NOT SUBMITTED, REVIEW FOR MANY OF THESE ITEMS CAN NOT |
| BE DONE AT THIS TIME. |
| |
| 5) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL |
| LOAD CALCULATIONS. THIS WAS NOT DONE, IN FACT NO LOAD |
| CALCULATIONS WERE SUBMITTED AND ONLY LOADS ON |
| CIRCUITING ON PANEL SCHEDULES WAS SHOWN. |
| PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 |
| 215.5, 230.42 ETC. |
| PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT |
| 125% 215.3, 230.42. THIS WAS SHOWN, HOWEVER PLEASE BE |
| SURE TO FIGURE INTO SERVICE. |
| ** PLEASE KNOW DEPENDING ON SERVICE, LOAD CALCULATIONS |
| FOR THE EXISTING SERVICE OR NEW PROPOSED *BUILDING* |
| SERVICE MAY BE NEEDED. AS NO INFORMATION FOR THE |
| *BUILDINGS* SERVICE WAS GIVEN WE CAN NOT DETERMINE MANY |
| THINGS. |
| |
| 6) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE |
| SUBMITTED. THIS NOTE REMAINS FROM PREVIOUS REVIEW AS |
| SOME ITEMS ARE MISSING FROM PLANS. |
| |
| 7) NOTE:PLEASE SEE NEW HORN/STROBES ARE SHOWN ON |
| PLANS HOWEVER NO MINIMUM LEVELS FOR ADA COMPLIANCE WAS |
| SHOWN.PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND |
| STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA |
| REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA |
| COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS |
| REQUIRED PER CODE IS NOT PERMITTED) |
| |
| ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL |
| BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY |
| SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT |
| REMOVE FROM SETS. |
| FBC 106.3.5.1.2 |
| |
| 8) NOTE:SAME NOTE FROM PREVIOUS REVIEW. NOTES WERE |
| PLACED ON PLANS HOWEVER THE INDICATE OF THESE BREAKERS |
| ON PANEL SCHEDULES COULD NOT BE LOCATED. PLEASE |
| INDICATE ALL SHUNT TRIP CIRCUITS FOR ANY ELECTRICAL |
| UNDER HOOD PER NFPA-96. CHAPTER 9 AND 10. |
| |
| 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI |
| PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS |
| WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS. PLEASE |
| SEE NOTES WERE ADDED AND MOST ARE SHOWN HOWEVER NOT |
| ALL. |
| |
| 10) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON |
| SERVICE PER 220.43B. |
| THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC |
| CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER |
| 13 ARE MORE RESTRICTIVE FOR LPD. |
| PLEASE SEE THIS IS THE SAME AS PREVIOUS REVIEW. |
| |
| 12) NOTE: PLEASE SEE THE SIGN CIRCUIT AND WINDOW |
| RECEPTACLES WERE ADDED TO PLANS HOWEVER PLEASE VERIFY |
| THE NEW LIGHTING SWITCHES BEING ADDED TO PLANS ARE |
| BEING SHOWN OUTSIDE THE FRONT OF THE STORE AS SHOWN ON |
| PLANS? |
| |
| 13) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| HEATER PER 422.30,.31 |
| MAY NOT QUOTE REQUIREMENT OR CODE. |
| |
| 14) NOTE: PLEASE SEE MISSING DISCONNECT FOR A/C CU PER |
| 440.11. |
| MAY NOT QUOTE REQUIREMENT OR CODE IN LIEU OF DETAIL. |
| |
| 15) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR CU. |
| 210.63,210.8B |
| |
| 16) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS NEW |
| HARD-WIRED SMOKE DETECTORS WHICH TO BE INSTALLED |
| HOWEVER NONE OF THESE COULD BE LOCATED ON PLANS ALONG |
| WITH CIRCUITING. IF A FA SYSTEM IS GOING TO BE |
| INSTALLED AS SHOWN ON PLANS, PLEASE SHOW HOW THESE SDS |
| WILL BE CONNECTED. |
| |
| 17) NOTE: PLEASE SEE THE CONDUCTORS ON PANEL SCHEDULE |
| FOR FEEDERS TO PANEL *B* ARE BEING SHOWN AS #12 WHEN |
| RISER SHOWS #3. |
| PLEASE SEE 240.4, 310.16. |
| |
| 18) NOTE: PLEASE SEE THE VALUE WAS STILL NOT ADJUSTED |
| ON PERMIT APPLICATION OR EVEN RESPONDED TO. PLEASE SEE |
| THE VALUATION FOR THE COMPLETE SCOPE OF WORK IS |
| EXTREMELY LOW. ALL VALUE SHALL BE BASED ON LABOR, |
| MATERIALS AND ALL PERMANENTLY INSTALLED EQUIPMENT EVEN |
| IF OWNER SUPPLIED. |
| FBC 108.3 |
| PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED |
| STANDARDS BY THE FBC MAY BE USED. |
| |
| 19) NOTE: PLEASE SEE THE NOC AS SUBMITTED HAS BECOME |
| VOID PER FS 713.13(2). THIS WILL BE NEEDED TO BE |
| RE-RECORDED AND SUBMITTED BEFORE PERMIT CAN BE PICKED |
| UP. PLEASE KNOW THAT ONCE A NOC HAS BEEN RECORDED, THE |
| SCOPE OF WORK MUST COMMENCE WITHIN 90DAYS OR THE NOC |
| BECOMES VOID. |
| |
| 20) NOTE: PLEASE SEE ATTACHED FS 553.80(2)(B) WITH |
| RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE AS |
| SEVERAL COMMENTS WERE REPEATED FROM PREVIOUS REVIEW. |
| PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |