Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-22 09:03:45*** UNSAT 2ND REVIEW ***
  
 *** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED AND THERE ARE SOME NEW COMMENTS DUE TO
 CHANGES IN PLANS. PLEASE SEE THAT MOST OF THE ITEMS ARE
 FROM PREVIOUS REVIEW.
  
 ** ONCE AGAIN, DUE TO THE AMOUNT OF COMMENTS AND
 UN-LICENSED INFORMATION, ONE SET OF PLANS ARE BEING
 RETAINED BY THIS OFFICE.
  
 1) NOTE:PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL
 FIRM. AS STATED ON PREVIOUS REVIEW NOT CERTIFICATE OF
 AUTHORIZATION NUMBER IS ON PLANS AND NOT INFORMATION ON
 THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 FROM THE STATE COULD BE LOCATED. PLANS ARE BEING
 RETAINED AND INFORMATION TO THE STATE BOARD OF
 ARCHITECTS AND STATE LEGAL COUNSEL TO THE BOARD WILL BE
 NOTIFIED.
 PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING THE
 REQUIRED LICENSURE PER FS 481.219 AND FAC 61G1-16.004.
 PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER REVIEWERS.
  
 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES,
 PANEL SCHEDULE AND PLANS.
 PLEASE SEE THE ELECTRICAL RISER IS STILL SHOWING A NEW
 SERVICE WHICH IS NOT PERMITTED AND IS NOT GRANTED BY
 THIS OFFICE. PLEASE SEE THE PREVIOUS NOTES ON PLANS HAD
 SOME DIFFERENCES IN THE SIZE OF SERVICE AND NOW THEY
 HAVE BEEN CHANGED BUT HOWEVER ARE STILL NOT CORRECT.
 PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A
 300A PANEL IN ONE NOTE, 200AMP IN ANOTHER NOTE.
 THIS LOCATION HAS BEEN LOOKED AT BY THIS OFFICE AND THE
 TENANT SPACE DOES NOT FALL UNDER THE DEFINITION OF A
 *BUILDING*. PLEASE SEE THAT COMPLETE INFORMATION FOR
 THE ENTIRE BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS
 TO BE A TENANT SPACE WHICH IS PART OF A LARGER
 BUILDING. PLEASE KNOW THAT ADDITIONAL SERVICE IS NOT
 BEING GRANTED AS IT DOES NOT MEET 230.2. THERE IS NO
 INDICATION ON PLANS WHICH SHOWS COMPLIANCE WITH THE FBC
 TO CONSIDER THIS A *SEPARATE BUILDING BY DEFINITION*.
 PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING
 WILL NEED TO UP-GRADED IF THE EXISTING SERVICE IS NOT
 OF SUFFICIENT SIZE.
 ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING
 SERVICE OR NEW. AS THE SERVICE AS PERMITTED HAS NOT
 BEEN SHOWN A REVIEW OF SERVICE CAN NOT BE DONE AT THIS
 TIME.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTES REQUESTED A
 COMPLETED RISER HOWEVER SOME OF THE INFORMATION IS
 STILL NOT ON PLANS. PLEASE SEE THE GROUNDING ELECTRODE
 SYSTEM AS REQUIRED PER 250.50 IS NOW SHOWING THE
 BUILDING/FOOTER STEEL? THIS IS AN EXISTING BUILDING AND
 THE EXISTING FOOTER STEEL IS NOT REQUIRED TO BE
 UNCOVERED IF THE ATTACHMENT IS NOT ALREADY MADE. THIS
 WOULD INDEED AFFECT THE STRUCTURAL INTEGRITY OF THE
 EXISTING FOOTER
 PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE
 EQUIPMENT.
 PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70
  
 4) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH
 THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13 AS
 PREVIOUSLY REQUESTED. PLEASE SEE 13-413.1ABC.1,
 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 13-415.1.AB.1.1, 13-415.2.
 PLEASE SEE A LIGHTING CONTROL PANEL IS NOW NOTED BUT
 THE NO INFORMATION WAS SHOWN FOR THE LIGHTING CONTROL
 PANEL OR SYSTEM.
 PLEASE SEE NOT TIMED SCHEDULING WAS SUBMITTED.
 PLEASE SEE NO TIMES WERE INDICATED FOR OVER RIDES.
 PLEASE SEE NO SPECIFIC TYPES OF DEVICES ARE INDICATED.
 PLEASE SEE ALL LOCATIONS FOR OVER RIDES ARE NOT SHOWN
 AS REQUIRED PER SECTIONS ABOVE.
 PLEASE SEE NOT ALL SEPARATE SPACES ARE SHOWING REQUIRED
 DEVICES.
 PLEASE SEE THE LIGHTING POWER DENSITIES ARE NOT
 CORRECT.
 PLEASE SEE TRACK LIGHTING PER 13-415.2.ABC.1.2 WAS NOT
 SHOWN OR CORRECT.
 PLEASE SEE13-415.2.ABC.1.2 (3, 4)
 NO FIXTURE LEGEND WAS SUBMITTED WHICH INDICATES THE
 FIXTURES AS NOTED ON PLANS, NO WATTAGE ON FIXTURES ETC
 NO ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS, ETC
 AS THERE IS MUCH INFORMATION FOR CHAPTER 13 WHICH WAS
 NOT SUBMITTED, REVIEW FOR MANY OF THESE ITEMS CAN NOT
 BE DONE AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL
 LOAD CALCULATIONS. THIS WAS NOT DONE, IN FACT NO LOAD
 CALCULATIONS WERE SUBMITTED AND ONLY LOADS ON
 CIRCUITING ON PANEL SCHEDULES WAS SHOWN.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43
 215.5, 230.42 ETC.
 PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT
 125% 215.3, 230.42. THIS WAS SHOWN, HOWEVER PLEASE BE
 SURE TO FIGURE INTO SERVICE.
 ** PLEASE KNOW DEPENDING ON SERVICE, LOAD CALCULATIONS
 FOR THE EXISTING SERVICE OR NEW PROPOSED *BUILDING*
 SERVICE MAY BE NEEDED. AS NO INFORMATION FOR THE
 *BUILDINGS* SERVICE WAS GIVEN WE CAN NOT DETERMINE MANY
 THINGS.
  
 6) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE
 SUBMITTED. THIS NOTE REMAINS FROM PREVIOUS REVIEW AS
 SOME ITEMS ARE MISSING FROM PLANS.
  
 7) NOTE:PLEASE SEE NEW HORN/STROBES ARE SHOWN ON
 PLANS HOWEVER NO MINIMUM LEVELS FOR ADA COMPLIANCE WAS
 SHOWN.PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND
 STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA
 COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS
 REQUIRED PER CODE IS NOT PERMITTED)
  
 ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL
 BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY
 SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT
 REMOVE FROM SETS.
 FBC 106.3.5.1.2
  
 8) NOTE:SAME NOTE FROM PREVIOUS REVIEW. NOTES WERE
 PLACED ON PLANS HOWEVER THE INDICATE OF THESE BREAKERS
 ON PANEL SCHEDULES COULD NOT BE LOCATED. PLEASE
 INDICATE ALL SHUNT TRIP CIRCUITS FOR ANY ELECTRICAL
 UNDER HOOD PER NFPA-96. CHAPTER 9 AND 10.
  
 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI
 PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS
 WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS. PLEASE
 SEE NOTES WERE ADDED AND MOST ARE SHOWN HOWEVER NOT
 ALL.
  
 10) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON
 SERVICE PER 220.43B.
 THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC
 CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER
 13 ARE MORE RESTRICTIVE FOR LPD.
 PLEASE SEE THIS IS THE SAME AS PREVIOUS REVIEW.
  
 12) NOTE: PLEASE SEE THE SIGN CIRCUIT AND WINDOW
 RECEPTACLES WERE ADDED TO PLANS HOWEVER PLEASE VERIFY
 THE NEW LIGHTING SWITCHES BEING ADDED TO PLANS ARE
 BEING SHOWN OUTSIDE THE FRONT OF THE STORE AS SHOWN ON
 PLANS?
  
 13) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER PER 422.30,.31
 MAY NOT QUOTE REQUIREMENT OR CODE.
  
 14) NOTE: PLEASE SEE MISSING DISCONNECT FOR A/C CU PER
 440.11.
 MAY NOT QUOTE REQUIREMENT OR CODE IN LIEU OF DETAIL.
  
 15) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR CU.
 210.63,210.8B
  
 16) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS NEW
 HARD-WIRED SMOKE DETECTORS WHICH TO BE INSTALLED
 HOWEVER NONE OF THESE COULD BE LOCATED ON PLANS ALONG
 WITH CIRCUITING. IF A FA SYSTEM IS GOING TO BE
 INSTALLED AS SHOWN ON PLANS, PLEASE SHOW HOW THESE SDS
 WILL BE CONNECTED.
  
 17) NOTE: PLEASE SEE THE CONDUCTORS ON PANEL SCHEDULE
 FOR FEEDERS TO PANEL *B* ARE BEING SHOWN AS #12 WHEN
 RISER SHOWS #3.
 PLEASE SEE 240.4, 310.16.
  
 18) NOTE: PLEASE SEE THE VALUE WAS STILL NOT ADJUSTED
 ON PERMIT APPLICATION OR EVEN RESPONDED TO. PLEASE SEE
 THE VALUATION FOR THE COMPLETE SCOPE OF WORK IS
 EXTREMELY LOW. ALL VALUE SHALL BE BASED ON LABOR,
 MATERIALS AND ALL PERMANENTLY INSTALLED EQUIPMENT EVEN
 IF OWNER SUPPLIED.
 FBC 108.3
 PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED
 STANDARDS BY THE FBC MAY BE USED.
  
 19) NOTE: PLEASE SEE THE NOC AS SUBMITTED HAS BECOME
 VOID PER FS 713.13(2). THIS WILL BE NEEDED TO BE
 RE-RECORDED AND SUBMITTED BEFORE PERMIT CAN BE PICKED
 UP. PLEASE KNOW THAT ONCE A NOC HAS BEEN RECORDED, THE
 SCOPE OF WORK MUST COMMENCE WITHIN 90DAYS OR THE NOC
 BECOMES VOID.
  
 20) NOTE: PLEASE SEE ATTACHED FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE AS
 SEVERAL COMMENTS WERE REPEATED FROM PREVIOUS REVIEW.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]