Date |
Text |
2007-06-21 14:28:29 | BUILDING PLAN REVIEW |
| PERMIT: 07031011 |
| ADD: 3010 S. DIXIE HWY |
| CONT: MIKE MOORE CONSTRUCTION |
| TEL: (561)748-7000 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 2ND |
| ACTION: DENIED |
| |
| **************NO RESPONSE WERE GIVEN*************** |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)61G1-16.004 TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| |
| 3)108.3* THE CLAIMED VALUATION ON THE PERMIT |
| APPLICATION IS LOW.IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRUCAL, GAS, MECHANICAL OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH ARCHITECTURAL AND DESIGN |
| FEES, MARKETING COST, AND OVERHEAD AND PROFIT EXCLUDING |
| LAND VALUE. |
| |
| 4)110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING. |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PROJECT WAS DESIGNED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| D) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| E) SQ. FT. FOOTPRINT |
| F) SQ. FT. UNDER ROOF (TOTAL) |
| G) OCCUPANT LOAD |
| |
| 5)11-4.32.2 SEATING. |
| IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE |
| PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH |
| CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE |
| THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). 11-4.32.3 |
| KNEE CLEARANCES.IF SEATING FOR PEOPLE IN WHEELCHAIRS IS |
| PROVIDED AT TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 |
| INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 |
| INCHES (485 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45 |
| ). SHOW HOW THE TABLES ON SHEET A-1 WILL MEET THE |
| REQUIREMENTS OF FIG 45 BY INDICATING THE DIMENTIONS OF |
| THE TABLEAND SHOWING THE CLEAR FLOOR SPACE ON THE |
| PLANS. |
| |
| 6)INDICATE THE TYPE OF ALTERATION OF THE PROJECT IN |
| ACCORDANCE WITH CH 3 OF THE 2004 FLORIDA EXISTING |
| BUILDING CODE. |
| |
| 7)FBC.1210.1 FLOORS. IN OTHER THAN DWELLING UNITS, |
| TOILET AND BATHING ROOM FLOORS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE |
| WALLS AT LEAST 6 INCHES (152 MM). |
| |
| 8)FBC.1210.2WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) |
| ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| |