Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop P
Sequence Number 1
Notes
Date Text
2007-05-14 15:55:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING
 APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S
 DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE
 APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2.
 PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO
 REFLECT THE CORRECT ADDRESS.
  
 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE
 ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE
 BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219,
 481.2055.
  
 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE
 SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP.
 ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY
 WPB.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT
 RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN
 WILLIAMS (561) 822-2284, [email protected]. THEIR FAX
 NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124.
 --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE,
 MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE
 ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).--
 THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE
 FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING
 VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III
 SECTION 9--124(7)(B).
  
 5. SHT A-2 ALL KITCHEN AREA FLOOR DRAINS SHALL CONNECT
 TO THE GREASE WASTE SYSTEM, NOT THE SANITARY AS SHOWN.
 ARTICLE III SECTION 90-124(7).
  
 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A
 FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE
 FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 7. SHT A-2 THE HAND SINK NEXT TO PLUMBING PLAN KEY ITEM
 #14 SHALL DRAIN INDIRECTLY INTO A FLOOR SINK, AND SHALL
 CONNECT TO THE GREASE WASTE SYSTEM.SECTION802.1.1.
 AS SHOWN THE HAND SINK IS DRAINING THRU THE WET VENT
 FOR THE BATHROOM FIXTURES WHICH IS NOT ALLOWED. SECTION
 909.1.
  
 8. SHT A-2 THE FLOOR DRAIN IN THE ACCESSIBLE TOILET
 ROOM IS NOT VENTED AS SHOWN. THE FLOOR DRAIN SHALL BE
 TAKEN OFF THE VENTED LINE TO THE LAV. SECTION 901.2.1.
  
 9. SHT A-2 THE LAV STACK FOR THE ACCESSIBLE TOILET ROOM
 DOES NOT REFLECT THE PIPING LAYOUT ON THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 10. SHT A-2 INDICATE WHERE THE CONDENSATE FROM THE
 WALK-IN FREEZER AND THE WALK-IN REFRIDGERATOR DRAIN. AN
 INDIRECT WASTE RECEPTOR COMPLYING WITH SECTIONS 802.3
 OR 802.3.2 SHALL BE REQUIRED FOR THE DRAINAGE OF THE
 CONDENSATE.
  
 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS,
 (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT
 IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER
 TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV
 BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO
 BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION
 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9
  
 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE METHOD.
  
 13. SHT A-2 PLUMBING PLAN KEY #6 IS NOT APPROVED.
 PLEASE DELETE FROM REFERENCE. ARTICLE III SECTION
 90-124(7)(B)(F).
  
 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAV
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO
 BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR
 FLOOR SPACE REQUIRED FOR THE LAV).
  
 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. INDICATED ON THE
 PLANS AS 5PSI. PLEASE VERIFY WITH GAS PROVIDER. IF MORE
 THAN 1/2PSI, SHOW THE LOCATION OF ALL GAS REGULATORS
 AND SUBMIT THE MANUF. SPECIFICATION SHEETS INDICATING
 THE MODEL NUMBER OF THE REGULATOR. PLEASE INDICATE IF
 THE REGULATOR SHALL BE VENTED, AND IF SO SHOW THE
 ROUTING OF THE VENTING AND INDICATE THE MATERIAL FOR
 THE VENT. (VENT SHALL BE OF NON-COMBUSTALBE MATERIAL).
 REGULATORS SHALL BE DOWNSTREAM OF THE SOV OF THE GAS
 APPLIANCE.
  
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved