Date |
Text |
2007-05-14 15:55:28 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| CITY WPB MUNICIPAL CODE |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING |
| APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S |
| DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE |
| APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2. |
| PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO |
| REFLECT THE CORRECT ADDRESS. |
| |
| 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF |
| AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE |
| ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE |
| BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219, |
| 481.2055. |
| |
| 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS |
| REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE |
| SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP. |
| ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO |
| EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY |
| WPB. |
| |
| 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY |
| THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT |
| RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN |
| WILLIAMS (561) 822-2284, [email protected]. THEIR FAX |
| NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124. |
| --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE, |
| MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE |
| ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).-- |
| THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE |
| FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING |
| VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III |
| SECTION 9--124(7)(B). |
| |
| 5. SHT A-2 ALL KITCHEN AREA FLOOR DRAINS SHALL CONNECT |
| TO THE GREASE WASTE SYSTEM, NOT THE SANITARY AS SHOWN. |
| ARTICLE III SECTION 90-124(7). |
| |
| 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A |
| FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE |
| FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| |
| 7. SHT A-2 THE HAND SINK NEXT TO PLUMBING PLAN KEY ITEM |
| #14 SHALL DRAIN INDIRECTLY INTO A FLOOR SINK, AND SHALL |
| CONNECT TO THE GREASE WASTE SYSTEM.SECTION802.1.1. |
| AS SHOWN THE HAND SINK IS DRAINING THRU THE WET VENT |
| FOR THE BATHROOM FIXTURES WHICH IS NOT ALLOWED. SECTION |
| 909.1. |
| |
| 8. SHT A-2 THE FLOOR DRAIN IN THE ACCESSIBLE TOILET |
| ROOM IS NOT VENTED AS SHOWN. THE FLOOR DRAIN SHALL BE |
| TAKEN OFF THE VENTED LINE TO THE LAV. SECTION 901.2.1. |
| |
| 9. SHT A-2 THE LAV STACK FOR THE ACCESSIBLE TOILET ROOM |
| DOES NOT REFLECT THE PIPING LAYOUT ON THE FLOOR PLAN. |
| PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 10. SHT A-2 INDICATE WHERE THE CONDENSATE FROM THE |
| WALK-IN FREEZER AND THE WALK-IN REFRIDGERATOR DRAIN. AN |
| INDIRECT WASTE RECEPTOR COMPLYING WITH SECTIONS 802.3 |
| OR 802.3.2 SHALL BE REQUIRED FOR THE DRAINAGE OF THE |
| CONDENSATE. |
| |
| 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL |
| PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS, |
| (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT |
| IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER |
| TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV |
| BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO |
| BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION |
| 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9 |
| |
| 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER |
| SECTION 607.3.2. PLEASE INDICATE METHOD. |
| |
| 13. SHT A-2 PLUMBING PLAN KEY #6 IS NOT APPROVED. |
| PLEASE DELETE FROM REFERENCE. ARTICLE III SECTION |
| 90-124(7)(B)(F). |
| |
| 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW |
| COMPLIANCE WITH THE FOLLOWING: |
| ___FOR W/C |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.5 FLUSH CONTROLS |
| ___FOR LAV |
| A. 11-4.19.3 CLEAR FLOOR SPACE |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE |
| CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO |
| BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF |
| THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR |
| FLOOR SPACE REQUIRED FOR THE LAV). |
| |
| 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED |
| LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL |
| AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & |
| 409.5. |
| |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| C. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. INDICATED ON THE |
| PLANS AS 5PSI. PLEASE VERIFY WITH GAS PROVIDER. IF MORE |
| THAN 1/2PSI, SHOW THE LOCATION OF ALL GAS REGULATORS |
| AND SUBMIT THE MANUF. SPECIFICATION SHEETS INDICATING |
| THE MODEL NUMBER OF THE REGULATOR. PLEASE INDICATE IF |
| THE REGULATOR SHALL BE VENTED, AND IF SO SHOW THE |
| ROUTING OF THE VENTING AND INDICATE THE MATERIAL FOR |
| THE VENT. (VENT SHALL BE OF NON-COMBUSTALBE MATERIAL). |
| REGULATORS SHALL BE DOWNSTREAM OF THE SOV OF THE GAS |
| APPLIANCE. |
| |
| D. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| |
| E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| F. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| F. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |
| |
| |
| . |