Notes |
Date |
Text |
2007-04-17 08:46:53 | *** DENIED *** | | 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 | | FBC 13-607.1.ABC.1 . | | | | 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS, SEE 2004 | | FBC/M 401.2. | | | | 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS SHOWING | | EXISTING AND NEW DUCT LAY-OUT WITH AN A/C EQUIPMENT | | SCHEDULE, SEE 2004 FBC 106.3.5. | | | | 4) SEE ELECTRICAL REVIEW NOTES 13 AND 14, PLEASE | | CORRECT. | | | | 5) PLEASE BE AWARE A MECHANICAL A/C PERMIT WILL BE | | REQUIRED FOR BATHROOM EXHAUST FANS AND ANY OTHER A/C | | WORK TO BE DONE. | | | | 6) PLEASE BE AWARE ADDITIONAL MECHANICAL PERMITS WILL | | BE REQUIRED FORWALK-IN-COOLER AND FREEZER. PLANS FOR | | COOLER/FREEZER MAY BE SUBMITTEDWITH APPLICATION WHEN | | APPLYING FOR THAT PERMIT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|