Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-17 08:46:53*** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1 .
  
 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS, SEE 2004
 FBC/M 401.2.
  
 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS SHOWING
 EXISTING AND NEW DUCT LAY-OUT WITH AN A/C EQUIPMENT
 SCHEDULE, SEE 2004 FBC 106.3.5.
  
 4) SEE ELECTRICAL REVIEW NOTES 13 AND 14, PLEASE
 CORRECT.
  
 5) PLEASE BE AWARE A MECHANICAL A/C PERMIT WILL BE
 REQUIRED FOR BATHROOM EXHAUST FANS AND ANY OTHER A/C
 WORK TO BE DONE.
  
 6) PLEASE BE AWARE ADDITIONAL MECHANICAL PERMITS WILL
 BE REQUIRED FORWALK-IN-COOLER AND FREEZER. PLANS FOR
 COOLER/FREEZER MAY BE SUBMITTEDWITH APPLICATION WHEN
 APPLYING FOR THAT PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.