2007-05-17 13:25:25*****DENIED*****
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING STREETS, ROADS,
 FIRE LANES).
  
 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.ON THE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE
 HIGHWAY, DISPLAY THE NUMERICAL ADDRESS FOR THIS
 PROJECT.AS PER WEST PALM BEACH CODE, ADDRESS NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 6.PLEASE GIVE THE FOLLOWING INFORMATION:* OCCUPANCY
 TYPE, * OCCUPANT LOAD, * FIRE SPRINKLERED OR NOT, *
 INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND CEILINGS
 MATERIALS
  
 7.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96. SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 8.PLEASE BE ADVISED THAT THE SUBMITTED SUB-PERMIT
 PLANS FOR THE COOKING HOOD INSTALLATION AND THE COOKING
 HOOD SUPPRESSION SYSTEM WILL NOT BE REVIEWED UNTIL SUCH
 TIME THAT THE "MASTER" PERMIT HAS BEEN ISSUED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722