Date |
Text |
2007-04-15 19:08:48 | ** UNSAT ** |
| |
| ** PLEASE KNOW THAT PLANS ARE NOT COMPLETE AT THIS TIME |
| FOR A FULL AND COMPLETE REVIEW. THERE MAY VERY WELL BE |
| NEW COMMENTS ONCE PLANS ARE COMPLETED FOR REVIEW. |
| |
| ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLANS AT THIS TIME DO NOT INDICATE ANY CODES. PLEASE |
| SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 |
| FBC FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW |
| THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS |
| FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES, |
| PANEL SCHEDULE AND PLANS. |
| PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A |
| 400A PANEL IN ONE NOTE, 300AMP IN ANOTHER NOTE, 300A ON |
| PANEL SCHEDULE, YET RISER DOES NOT MATCH ANY OF THESE? |
| PLEASE SEE THAT COMPLETE INFORMATION FOR THE ENTIRE |
| BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS TO BE A |
| TENANT SPACE WHICH IS PART OF A LARGER BUILDING. PLEASE |
| KNOW THAT ADDITIONAL SERVICE IS NOT BEING GRANTED AS IT |
| DOES NOT MEET 230.2. THERE IS NO INDICATION ON PLANS |
| WHICH SHOWS COMPLIANCE WITH THE FBC TO CONSIDER THIS A |
| *SEPARATE BUILDING BY DEFINITION*. |
| PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING |
| WILL NEED TO UPGRADED IF THE EXISTING SERVICE IS NOT OF |
| SUFFICIENT SIZE. |
| ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING |
| SERVICE OR NEW. |
| PLEASE INCLUDE GROUNDING ELECTRODE SYSTEM AS REQUIRED |
| PER 250.50. (QUOTING THE CODE IS NOT PERMITTED IN LIEU |
| OF REQUIRED CODE COMPLIANT DETAIL) |
| PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE |
| EQUIPMENT. |
| PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70 ETC A |
| REVIEW FOR SERVICE CAN NOT BE DONE AT THIS TIME. |
| |
| 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH |
| THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. PLEASE |
| SEE 13-413.1ABC.1, 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE 13-415.1.AB.1.1, 13-415.2. |
| PLEASE INDICATE ALL MAXIMUM TIMES ON OVER RIDE DEVICES. |
| PLEASE SUBMIT DETAILS ON METHODS WHICH WILL BE |
| INSTALLED. |
| PLEASE SEE13-415.2.ABC.1.2 (3, 4) |
| NO FIXTURE LEGEND WAS SUBMITTED, NO ENERGY |
| CALCULATIONS, NO PERFORMANCE CALCULATIONS, ETC |
| AS NO INFORMATION FOR CHAPTER 13 WAS SUBMITTED, REVIEW |
| FOR THESE ITEMS CAN NOT BE DONE AT THIS TIME. |
| |
| 4) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL |
| LOAD CALCULATIONS. |
| PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 |
| 215.5, 230.42 ETC. |
| PLEASE SEE THERE ARE CIRCUITS WHICH ARE OVER LOADED. |
| PLEASE SEE NO LOADS ARE SHOWN FOR COMMERCIAL |
| APPLICATION. |
| PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT |
| 125% 215.3, 230.42 |
| |
| 5) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE |
| SUBMITTED. |
| PLEASE SEE 408.4 OF THE NEC, AND THE FOLLOWING TEXT |
| BELOW WHICH IS TAKEN DIRECTLY FROM THE NEC. |
| PLEASE KNOW THAT THE PLANS NEED TO LABEL AND PROVIDE |
| ROOM AND AREA DESIGNATIONS ON PLANS AND CORRELATE WITH |
| THE PANEL SCHEDULES SHOWING ALL ROOMS AND AREAS IN |
| WHICH CIRCUITS FEED WILL BE REQUIRED FOR EACH PANEL. |
| PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE |
| CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| ACCEPTABLE |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 6) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY |
| AND EXIT LIGHTS. |
| |
| 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA |
| COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS |
| REQUIRED PER CODE IS NOT PERMITTED) |
| |
| ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL |
| BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY |
| SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT |
| REMOVE FROM SETS. |
| FBC 106.3.5.1.2 |
| |
| 8) NOTE: PLEASE INDICATE ALL SHUNT TRIP CIRCUITS FOR |
| ANY ELECTRICAL UNDER HOOD PER NFPA-96. CHAPTER 9 AND |
| 10. |
| |
| 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI |
| PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS |
| WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS. |
| |
| 10) NOTE: PLEASE SEE SOME LOADS ON PANEL EXCEED THAT OF |
| THE RATED 20AMP CIRCUIT. |
| PLEASE SEE SHOW WINDOWS. |
| PLEASE INDICATE THE LOADS ON SHOW WINDOWS FOR BRANCH |
| CIRCUITS AND FEEDERS/SERVICE PER 220.43 |
| |
| 11) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON |
| SERVICE PER 220.43B. |
| THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC |
| CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER |
| 13 ARE MORE RESTRICTIVE. |
| |
| 12) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT AND |
| LOADS IN CALCULATIONS. |
| |
| 13) NOTE: PLEASE SEE THE VALUATION FOR THE COMPLETE |
| SCOPE OF WORK IS EXTREMELY LOW. ALL VALUE SHALL BE |
| BASED ON LABOR, MATERIALS AND ALL PERMANENTLY INSTALLED |
| EQUIPMENT EVEN IF OWNER SUPPLIED. |
| FBC 108.3 |
| PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED |
| STANDARDS BY THE FBC MAY BE USED. |
| |
| 14) NOTE: PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING |
| THE REQUIRED LICENSURE PER FS 481.219 AND FAC |
| 61G1-16.004. |
| PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER |
| OR NOT COMMENT IS MADE BY OTHER REVIEWERS. |
| |
| 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE(S) WITH ALL |
| BREAKER/OCP DEVICES AND CONDUCTOR SIZES. |
| 408.4. |
| 310.16, 240.4 |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| ** PLEASE KNOW DUE TO THE EXTENT OF ELECTRICAL |
| COMMENTS, NO LICENSING FOR THE ARCHITECTURAL FIRM, ONE |
| SET OF PLANS WILL BE RETAINED BY THIS OFFICE. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |