Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-15 19:08:48** UNSAT **
  
 ** PLEASE KNOW THAT PLANS ARE NOT COMPLETE AT THIS TIME
 FOR A FULL AND COMPLETE REVIEW. THERE MAY VERY WELL BE
 NEW COMMENTS ONCE PLANS ARE COMPLETED FOR REVIEW.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES. PLEASE
 SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004
 FBC FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW
 THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS
 FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES,
 PANEL SCHEDULE AND PLANS.
 PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A
 400A PANEL IN ONE NOTE, 300AMP IN ANOTHER NOTE, 300A ON
 PANEL SCHEDULE, YET RISER DOES NOT MATCH ANY OF THESE?
 PLEASE SEE THAT COMPLETE INFORMATION FOR THE ENTIRE
 BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS TO BE A
 TENANT SPACE WHICH IS PART OF A LARGER BUILDING. PLEASE
 KNOW THAT ADDITIONAL SERVICE IS NOT BEING GRANTED AS IT
 DOES NOT MEET 230.2. THERE IS NO INDICATION ON PLANS
 WHICH SHOWS COMPLIANCE WITH THE FBC TO CONSIDER THIS A
 *SEPARATE BUILDING BY DEFINITION*.
 PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING
 WILL NEED TO UPGRADED IF THE EXISTING SERVICE IS NOT OF
 SUFFICIENT SIZE.
 ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING
 SERVICE OR NEW.
 PLEASE INCLUDE GROUNDING ELECTRODE SYSTEM AS REQUIRED
 PER 250.50. (QUOTING THE CODE IS NOT PERMITTED IN LIEU
 OF REQUIRED CODE COMPLIANT DETAIL)
 PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE
 EQUIPMENT.
 PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70 ETC A
 REVIEW FOR SERVICE CAN NOT BE DONE AT THIS TIME.
  
 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH
 THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. PLEASE
 SEE 13-413.1ABC.1, 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2.
 PLEASE INDICATE ALL MAXIMUM TIMES ON OVER RIDE DEVICES.
 PLEASE SUBMIT DETAILS ON METHODS WHICH WILL BE
 INSTALLED.
 PLEASE SEE13-415.2.ABC.1.2 (3, 4)
 NO FIXTURE LEGEND WAS SUBMITTED, NO ENERGY
 CALCULATIONS, NO PERFORMANCE CALCULATIONS, ETC
 AS NO INFORMATION FOR CHAPTER 13 WAS SUBMITTED, REVIEW
 FOR THESE ITEMS CAN NOT BE DONE AT THIS TIME.
  
 4) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL
 LOAD CALCULATIONS.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43
 215.5, 230.42 ETC.
 PLEASE SEE THERE ARE CIRCUITS WHICH ARE OVER LOADED.
 PLEASE SEE NO LOADS ARE SHOWN FOR COMMERCIAL
 APPLICATION.
 PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT
 125% 215.3, 230.42
  
 5) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE
 SUBMITTED.
 PLEASE SEE 408.4 OF THE NEC, AND THE FOLLOWING TEXT
 BELOW WHICH IS TAKEN DIRECTLY FROM THE NEC.
 PLEASE KNOW THAT THE PLANS NEED TO LABEL AND PROVIDE
 ROOM AND AREA DESIGNATIONS ON PLANS AND CORRELATE WITH
 THE PANEL SCHEDULES SHOWING ALL ROOMS AND AREAS IN
 WHICH CIRCUITS FEED WILL BE REQUIRED FOR EACH PANEL.
 PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE
 CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA
 COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS
 REQUIRED PER CODE IS NOT PERMITTED)
  
 ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL
 BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY
 SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT
 REMOVE FROM SETS.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE INDICATE ALL SHUNT TRIP CIRCUITS FOR
 ANY ELECTRICAL UNDER HOOD PER NFPA-96. CHAPTER 9 AND
 10.
  
 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI
 PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS
 WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS.
  
 10) NOTE: PLEASE SEE SOME LOADS ON PANEL EXCEED THAT OF
 THE RATED 20AMP CIRCUIT.
 PLEASE SEE SHOW WINDOWS.
 PLEASE INDICATE THE LOADS ON SHOW WINDOWS FOR BRANCH
 CIRCUITS AND FEEDERS/SERVICE PER 220.43
  
 11) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON
 SERVICE PER 220.43B.
 THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC
 CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER
 13 ARE MORE RESTRICTIVE.
  
 12) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT AND
 LOADS IN CALCULATIONS.
  
 13) NOTE: PLEASE SEE THE VALUATION FOR THE COMPLETE
 SCOPE OF WORK IS EXTREMELY LOW. ALL VALUE SHALL BE
 BASED ON LABOR, MATERIALS AND ALL PERMANENTLY INSTALLED
 EQUIPMENT EVEN IF OWNER SUPPLIED.
 FBC 108.3
 PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED
 STANDARDS BY THE FBC MAY BE USED.
  
 14) NOTE: PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING
 THE REQUIRED LICENSURE PER FS 481.219 AND FAC
 61G1-16.004.
 PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER REVIEWERS.
  
 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE(S) WITH ALL
 BREAKER/OCP DEVICES AND CONDUCTOR SIZES.
 408.4.
 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2
  
 ** PLEASE KNOW DUE TO THE EXTENT OF ELECTRICAL
 COMMENTS, NO LICENSING FOR THE ARCHITECTURAL FIRM, ONE
 SET OF PLANS WILL BE RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]