Plan Review Notes
Plan Review Notes For Permit 07031011
Permit Number 07031011
Review Stop B
Sequence Number 1
Notes
Date Text
2007-05-31 14:59:03 
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07031011
 ADD: 3010 S. DIXIE HWY
 CONT: MIKE MOORE CONSTRUCTION
 TEL: (561)748-7000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3)108.3* THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW.IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRUCAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH ARCHITECTURAL AND DESIGN
 FEES, MARKETING COST, AND OVERHEAD AND PROFIT EXCLUDING
 LAND VALUE.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING.
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE DESIGN OCCUPANT LOAD, SEE 1004.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 E) SQ. FT. FOOTPRINT
 F) SQ. FT. UNDER ROOF (TOTAL)
 G) OCCUPANT LOAD
  
 5)11-4.32.2 SEATING.
 IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE
 PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH
 CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE
 THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). 11-4.32.3
 KNEE CLEARANCES.IF SEATING FOR PEOPLE IN WHEELCHAIRS IS
 PROVIDED AT TABLES OR COUNTERS, KNEE SPACES AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19
 INCHES (485 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45
 ). SHOW HOW THE TABLES ON SHEET A-1 WILL MEET THE
 REQUIREMENTS OF FIG 45 BY INDICATING THE DIMENTIONS OF
 THE TABLEAND SHOWING THE CLEAR FLOOR SPACE ON THE
 PLANS.
  
 6)INDICATE THE TYPE OF ALTERATION OF THE PROJECT IN
 ACCORDANCE WITH CH 3 OF THE 2004 FLORIDA EXISTING
 BUILDING CODE.
  
 7)FBC. 1210.1 FLOORS. IN OTHER THAN DWELLING UNITS,
 TOILET AND BATHING ROOM FLOORS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE
 WALLS AT LEAST 6 INCHES (152 MM).
  
 8)FBC. 1210.2WALLS WITHIN 2 FEET (610 MM) OF
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  